6–9

Calibration Instructions

Publication 1771-6.5.88 – July 1997

6. To calibrate the 4-20mA output range, first change the following

jumpers with power ON, then calibrate:

E6-E9 to the current position (left)

E6

E7

E8

E9

E10, E14, E13, E17 to the current position (top)

E17

E13

E14

E10

Step

Enter Command Code (BTW 2):

and Read in BTR:

1

0080H

word 4 = 0FFF

2

8080H

word 5 = 0FFF

7. To verify 4-20mA range, enter command codes 0400H and 8400H.

Then apply these codes for current:

Step

Apply Code for Current (BTW 3-6):

and Read Verification Code (BTR 10-13):

1

000H (4mA)

000H

2

0800H (12mA)

0800H

3

FFFH (20mA)

FFFH

8. To store the calibration data in EEPROM, follow these steps:

Step

Enter this Command Code (BTW 2):

1

0800H

2

8800H

3

0000H

ATTENTION: To avoid possible injury or machine damage
when you return the QDC module for service, make sure you
reset the jumpers to the original pre-calibration settings.

9. If there is no error in the BTR status byte, you completed the procedure.

Reset jumpers, re-assemble the module, and return it for service.