Calibration setup using optional equipment, Calibration setup at the machine location – Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual

Page 290

Advertising
background image

6–6

Calibration Instructions

Publication 1771-6.5.88 – July 1997

Set up your calibration equipment at a remote location as follows:

1. Install the PLC-5 processor in the I/O chassis.

2. Verify that you set all the QDC module’s jumpers to initial

calibration settings (see Set Internal Jumpers, above).

3. Install the QDC module circuit board with extender card in the

I/O chassis slot location corresponding to the module address of
your BTR and BTW instructions.

If you do not have an extender card, place the module circuit
board in the right-most slot so you can access the jumpers by
reaching inside the I/O chassis.

4. Connect the pre-wired input wiring arm to the module circuit board.

5. Connect other wiring as needed for the calibration setup.

6. Apply power.

7. Switch the PLC-5 processor to program mode and enter your

calibration ladder logic.

Set up your calibration equipment at your machine location as follows:

1. Remove all I/O modules from the I/O chassis.

2. Verify that you set all the QDC module’s jumpers to initial

calibration settings (see Set Internal Jumpers).

3. Install the QDC module circuit board in the right-most slot so you

can access the jumpers by reaching inside the I/O chassis. Be
sure the module address of your BTR and BTW instructions
matches the module’s slot location in the I/O chassis.

4. Wire the wiring arm and connect it to the QDC module circuit

board (see Wire the Wiring Arms, above).

5. Connect other wiring as needed for the calibration setup.

6. Apply power.

7. Switch the PLC-5 processor to program mode and disable your

entire ladder logic program by inserting a jump to label around
the application program.

8. Enter your calibration ladder logic.

Calibration Setup Using
Optional Equipment

Calibration Setup at the
Machine Location