Cpc - clamp close profile block, Cpc – clamp close profile block – Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual

Page 74

Advertising
background image

2–8

Command Word/Bit Descriptions

Publication 1771-6.5.88 – July 1997

Notes: 1. For [ ] engineering units, see page 3.

2. When using the Inject/Clamp/Eject mode, all pressure readings are system pressure at input 2, except where noted.

Word

Description

CLC41

Ejector Full Retract Segment 3

CLC42

Reserved

CLC43 - 64

Open

Bit-mapped Control Words

Word

Bit

Description

CPC01

Block ID = 00000111 (low byte). High byte reserved for the module. Do not use.

CPC02

Open

CPC03

Configuration Selections

Profile Algorithm Selections

B00

= 0 Vel/Pos selected for First Clamp Close Profile
= 1 Press/Pos selected for First Clamp Close Profile

B01

Open

B02

= 0 Vel/Pos selected for Second Clamp Close Profile
= 1 Press/Pos selected for Second Clamp Close Profile

B03

Open

B04

= 0 Vel/Pos selected for Third Clamp Close Profile
= 1 Press/Pos selected for Third Clamp Close Profile

B05-B07

Open

B08

First/Second Clamp Close Logical Bridge Selection
= 0 Start Second Clamp Close Profile at End of First Clamp Close Profile
= 1 Stop and Set-output at End of First Clamp Close Profile
The module checks this pause bit at end of the First Clamp Close Profile to determine what further action to take:
if B08 is:

then the module:

SET

sets its outputs to FCC33 - FCC40

RESET and CPC20 > 00000

immediately begins the Second Clamp Close Profile

RESET and CPC20 = 00000

reacts as if it had just completed the Second Clamp Close Profile, and
continues operation based on the state of CPC03-B09

B09

Second/Third Clamp Close Logical Bridge Selection
= 0 Start Third Clamp Close Profile at End of Second Clamp Close Profile
= 1 Stop and Set-output at End of Second Clamp Close Profile
The module checks this pause bit at end of the Second Clamp Close Profile to determine what further action to take:
if B09 is:

then the module:

SET

sets its outputs to SCC33 - SCC40

RESET and CPC29 > 00000

immediately begins the Second Clamp Close Profile

RESET and CPC29 = 00000

reacts as if it had just completed the Second Clamp Close Profile, and
continues operation based on the state of CPC03-B10

B10

Third Clamp Close/Clamp Low Press Close (LPC) Logical Bridge Selection
= 0 Start Clamp LPC Profile at End of Third Clamp Close Profile
= 1 Stop and Set-output at End of Third Clamp Close Profile
The module checks this pause bit at end of the Third Clamp Close Profile to determine what further action to take:
if B10 is:

then the module:

SET

sets its outputs to TCC33 - TCC40

RESET

immediately begins the Clamp Low Pressure Close Profile

CPC – Clamp Close
Profile Block