Osc - clamp open slow configuration block, Osc – clamp open slow configuration block – Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual

Page 145

Advertising
background image

2–79

Command Word/Bit Descriptions

Publication 1771-6.5.88 – July 1997

OSC

Bit-mapped Control Words

Word

Bit

Description

OSC01

Block ID = 0010100 (Low byte). High byte reserved for the module. Do not use.

OSC02

Configuration Selections

B00-B02

Selected Velocity Control Valve
The module uses its algorithm to drive the following output during any Vel/Pos Clamp Open Slow Profile.
B02 B01 B00
0 0 0 Output #1
0 0 1 Output #2
0 1 0 Output #3
0 1 1 Output #4
1 0 0 Output #5
1 0 1 Output #6
1 1 0 Output #7
1 1 1 Output #8

B03

Open

B04-B06

Selected Pressure Control Valve
The module uses its algorithm to drive the following output during any Press/Pos Clamp Open Slow Profile.
B06 B05 B04
0 0 0 Output #1
0 0 1 Output #2
0 1 0 Output #3
0 1 1 Output #4
1 0 0 Output #5
1 0 1 Output #6
1 1 0 Output #7
1 1 1 Output #8

B07

Pressure Algorithm Selection
= 0 Dependent Gains (ISA)
= 1 Independent Gains (A-B)

B08-B15

Open

OSC03 - 04

Open

Expert Response Compensation (ERC) Percentage

Word

Description

OSC05

Minimum Velocity Control ERC Percentage [31]
Although error coding allows range of 00000 to 09999, the module limits it to a minimum of 01000.

OSC06

Minimum Pressure Control ERC Percentage [31]
Although error coding allows range of 00000 to 09999, the module limits it to a minimum of 01000.

OSC07

Open

Watchdog Timer

Word

Description

OSC08

Profile Watchdog Timer Preset [21] When the module starts the Clamp Open Slow Profile, it:

S

starts an internal Profile Watchdog timer

S

stops this timer and reset its accumulated value to zero (after reporting total execution time in OPS60) when it completes the profile

S

sets master status bit SYS04-B13 when the accumulated value of this timer equals or exceeds this entry.

A zero entry inhibits SYS04-B13.

OSC – Clamp Open Slow
Configuration Block