Changing parameter settings or values, 5 using the optional hoa keypad – Yaskawa iQpump Micro User Manual

Page 100

Advertising
background image

Figure 4.12 Home Quick Monitor Screen

The following monitors are available via the Quick Monitor:

Monitor

Name

U1-01

Frequency Reference

U5-99

Auto Setpoint

U1-02

Output Frequency

U1-03

Output Current

U1-06

Output Voltage

U1-07

DC Bus Voltage

U1-08

Output Power

U1-10

Input Terminal Status

Monitor

Name

U1-11

Output Terminal Status

U1-13

Terminal A1 Level

U1-14

Terminal A2 Level

U1-25

CPU 1 SW Number

U4-01

Drive Elapsed Time

U9-02

iQ Network Activity

U1-99

Anti-No-Flow Timer

u

Changing Parameter Settings or Values

This example explains changing C1-02 (Deceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.

Note:

During serial communication writing, if a parameter change is also attempted via the HOA keypad, a “BUSY - WRITE PROTECTED”

message will display. Parameter change will not be possible from the HOA keypad until an Enter command is received via the serial

communication to finish the serial writing process.

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U5-99= 0.0PSI
U1-02= 0.00Hz

U1-91= 0.0PSI

DRV

Auto Setpoint

Rdy

<-MONITOR->

LSEQ

LREF

2. Press

or

until the Parameter Setting Mode screen appears.

Home

- MODE -

PRG

Programming

FWD

3. Press

to enter the parameter menu tree.

-PRMSET-

Initialization

Select Language

PRG

FWD

A

1-00= 0

Home

DATA

4. Press

or

to select the C parameter group.

-PRMSET-

Basic Setup

Accel Time 1

PRG

FWD

C

1-01=

20.0 sec

FWD

Home

DATA

5. Press

two times.

-PRMSET-

Accel/Decel

Accel Time 1

PRG

FWD

C

1

-01=

20.0sec

-PRMSET-

C1-

01

= 20.0sec

(0.0~6000.0)

“20.0 sec”

PRG

Accel Time 1

FWD

Home

Home

DATA

DATA

4.5 Using the Optional HOA Keypad

100

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual