No.

Display

Name

Function

16

Communication Port

Port used for USB Copy Unit, LCD Operator Keypad, and for connecting to a PC.

NOTICE: Use only specified cable when making connections to the drive.

Failure to comply may damage the drive.

NOTICE: Do not open the port cover wider than 90 degrees. Failure to

comply may break the port cover and leave the unprotected port susceptible

to damage.

u

LED Screen Displays

Display

Lit

Flashing

Off

When the drive detects an alarm or error

• When an alarm occurs
• oPE detected
• When a fault or error occurs during

Auto-Tuning

Normal state (no fault or alarm)

Motor is rotating in reverse

Motor is rotating forward

Drive Mode

Auto-Tuning

Programming Mode

Displays output frequency (Hz)

As illustrated in

this manual

STOP

u

AUTO LED and HAND LED Indications

Table 4.2 AUTO LED and HAND LED Indications

AUTO LED

HAND LED

State

AUTO

Off

HAND

Off

OFF mode

AUTO

Off

HAND

On solid

HAND mode

AUTO

Off

HAND

Long blink (50% duty)

HAND mode when the Frequency Reference is 0 and/or decelerating in HAND mode.

AUTO

On solid

HAND

Off

Running in AUTO mode

AUTO

Long blink (50% duty)

HAND

Off

Running in AUTO mode when the Frequency Reference is 0 and/or decelerating in AUTO

mode.

AUTO

Short blink (15% duty)

HAND

Off

AUTO mode, Ready, No run command input.

AUTO

Double blink

HAND

Off

AUTO mode, stopped by a Fast- Stop from a Multi-Function Digital Input.

Flashing

ON

ON

ON

ON

ON

ON

1 s

Flashing
quickly

Figure 4.1 AUTO LED and OFF LED Status and Meaning