1 standard connection diagram – Yaskawa iQpump Micro User Manual

Page 62

Advertising
background image

<1> Remove the jumper when installing an optional DC link choke.
<2> The MC on the input side of the main circuit should open when the thermal relay is triggered.
<3> Self-cooled motors do not require separate cooling fan motor wiring.
<4> Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink mode (0 V com).
<5> Use only a +24 V internal power supply in sinking mode; the source mode requires an external power supply.
<6> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters and wattmeters; they are not

intended for use as a feedback-type of signal.
<7> Disconnect the wire jumper between HC and H1 when utilizing the safety input.

Refer to Wiring the Control Circuit

Terminal on page 77

for details on removing the jumper. The wire length for the Safe Disable input should not exceed

30 m.
<8> Note that if the drive is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a

sequence to interrupt power when a fault occurs will result in shutting off the power to the drive as the drive attempts to restart

itself. The default setting for L5-02 is 0 (fault output active during restart attempt).

WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameter is

properly set (S5 for 3-Wire; H1-05 = “0”). Improper sequencing of run/stop circuitry could result in death or serious injury from moving

equipment.

WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing

the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary

closure on terminal S1 may cause the drive to start.

WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control terminals and ensure parameter

b1-17 is set to 0 (drive does not accept a run command at power up (default). If the drive is wired for 3-Wire sequence but set up for 2-Wire

sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction

at power up of the drive and may cause injury.

WARNING! When the application preset function is executed (or A1-06 is set to any value other than 0) the drive I/O terminal functions

change. This may cause unexpected operation and potential damage to equipment or injury.

Figure 3.2

illustrates an example of a 3-Wire sequence.

Drive

Sequence input common

Run relay (N.O.)

Stop relay (N.C.)

Run command (run on momentary close)

Stop command (stop on momentary open)

Foward/reverse command
(multi-function input: H1-05 = 0)

S1

S2

S5

SC

Figure 3.2 3-Wire Sequence

3.1 Standard Connection Diagram

62

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual