Yaskawa iQpump Micro User Manual

Page 109

Advertising
background image

H1 Multi-Function Digital Input Settings

H1-oo

Setting

Function

Description

73

Low City Press

Indicates that sufficient or insufficient pressure is present on the inlet to the pump. Used mainly for pressure

booster situations.

Digital Operator Display

Minor Fault Name

Low City Pressure

(LCP)

Low City Pressure

Cause

Possible Solution

Insufficient pressure is present on the inlet

to the pump.

Shown when P4-24 = 0 and when the digital

input has been active (closed for P4-21 = 0,

or open for P4-21 = 1) for the time set in

P4-22.

• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.

Digital Operator Display

Minor Fault Name

Low Suction Pressure

(LSP)

Low Suction Pressure

Cause

Possible Solution

Insufficient suction pressure is present.

Shown when P4-24 = 1 and when the digital input has been active (closed for P4-21 = 0, or open for P4-21

= 1) for the time set in P4-22.

The drive, if running, coasts-to-stop and does not run until the digital input has been inactive for the time

set in P4-22.

Digital Operator Display

Minor Fault Name

Low Water in Tank

(LWT)

Low Water in Tank

Cause

Possible Solution

The water level in the tank is too low.

Shown when P4-24 = 2 and when the digital

input has been active (closed for P4-21 = 0,

or open for P4-21 = 1) for the time set in

P4-22.

• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.
• Raise the water level.

n

Current Limit

This function provides a current limit of the pump (motor). The function is designed to prevent long-term overload conditions

of the pump, especially if the motor and drive are oversized compared to the pump. The drive will attempt to limit the output

current by reducing the frequency reference. The frequency is reduced using an internal current PID regulator. When the

Current Limit function is active, the alarm "Current Limit Foldback" or “CUr” will be displayed on the digital operator keypad.

This function will only operate correctly when the drive is connected to a variable torque motor load such as a centrifugal

pump. More specifically, it will only operate if the load is such that output current increases as output frequency increases

(and vice-versa). The current limit function reduces the pump speed to just above the lower value between the minimum pump

speed (P1-06) or the minimum output frequency. If PID mode is enabled (b5-01 > 0), a special limit will be applied to the PID

integrator when output current limit is active to prevent integrator wind-up.
Current Limit Foldback
(CUr)

Start Up Procedure

1.

Set all other parameters required for the application such as PID control loop, sleep, motor, and I/O parameters

2.

Turn on the current limit function by setting Q3-01 to 1 (enabled). The default setting is 0 (disabled).

3.

Set the desired current limit in Q3-02. This value should not exceed the motor, pump or drive ratings. This does not

change the motor (oL1) or drive (oL2) overload functions.

4.

If desired, program a multi-function digital output (H2-oo) to 89 (Output Current Limit) to annunciate the alarm.

Related Parameters

No.

Parameter Name

Setting Values

Q3-01

Output Current Limit Select

Default: 0

Range: 0, 1

Q3-02

Current Limit

Default: 0.0 A

Min.: 0.0

Max.: 1000.0

4.7 iQpump Presets and Functions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

109

4

Start-Up Programming & Operation

Advertising
This manual is related to the following products: