Digital Operator Display

Minor Fault Name

oL4

Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable

time (L6-06).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check the settings of parameters L6-05 and L6-06.

Digital Operator Display

Minor Fault Name

ov

DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
• For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 < 400)

Cause

Possible Solutions

Surge voltage present in the drive input

power.

• Install a DC link choke or an AC reactor.
• Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same

drive input power system.

The motor is short-circuited.

• Check the motor power cable, relay terminals and motor terminal box for short circuits.
• Correct grounding shorts and turn the power back on.

Ground current has overcharged the main

circuit capacitors via the drive input power.

Noise interference causes the drive to

operate incorrectly.

• Review possible solutions for handling noise interference.
• Review section on handling noise interference and check control circuit lines, main circuit lines and ground

wiring.

• If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil.
Set number of fault restarts (L5-01) to a value other than 0.

Digital Operator Display

Minor Fault Name

Pump Cycling

Pump Over Cycle

(PCyC)

Pump Over Cycle

Cause

Possible Solution

The pump has exceeded the number of

cycles set in P2-10 in the time set in P2-11

and P2-12 is set to 1 (alarm).

• Set the Pump Over Cycle alarm characteristics in P2-10 and P2-11.
• Drive response to this condition is controlled by P2-12, Over Cycling Mode.

Digital Operator Display

Minor Fault Name

R-DNE-So

(Rdd)

Remote Drive Disable

Cause

Possible Solution

Terminal So (H1-0o = 95) has been

closed for the time set in P4-26, Remote

Drive Disable On-Delay, when P4-25,

Remote Drive Disable Selection, was set to

0 (N.O.).

Remove conditions causing the terminal to close.

Terminal So (H1-0o = 95) has been open

for the time set in P4-26, Remote Drive

Disable On-Delay, when P4-25, Remote

Drive Disable Selection, was set to 1

(N.C.).

Remove conditions causing the terminal to open.

Digital Operator Display

Minor Fault Name

SE

MEMOBUS/Modbus Communication Test Mode Error

Note:

This alarm will not trigger a multi-function output terminal that is set for alarm output

(H2-oo = 10).

Cause

Possible Solution

A digital input set to 67H (MEMOBUS/

Modbus test) was closed while the drive

was running.

Stop the drive and run the test again.

5.3 Alarm Detection

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

189

5

Troubleshooting