7 iqpump presets and functions – Yaskawa iQpump Micro User Manual

Page 116

Advertising
background image

• Decrease the lag fixed speed delay (P9-07)
• Increase the staging frequency level (P9-09)
• Increase the staging delay time (P9-11)
• Increase the de-staging delay time (P9-15)
• Increase the stabilization time (P9-16)
• Increase both the Add Freq Level and Add Dly Time

Table 4.12 Related Parameters for Duplex System with Fine Tuning Application Example

Description

Drive A

<1>

Drive B

<1>

Run Source: 1 (Terminals)

b1-02 = 1

b1-02 = 1

Node Address

H5-01 = 1

H5-01 = 2

Highest Node Address

P9-25 = 2

P9-25 = 2

Pump Mode: 3 (Network)

P1-01 = 3

P1-01 = 3

Feedback Source: 0 (Analog)

P9-02 = 0

P9-02 = 0

Lag Fixed Speed

P9-06 = 54.0 Hz

P9-06 = 54.0 Hz

Setpoint

U5-99 = 100 PSI

U5-99 = 100 PSI

Start Level

P1-04 = 140 PSI

P1-04 = 140 PSI

High Feedback Quick De-Stage

P9-18 = 89.3%

P9-18 = 89.3%

Setpoint Modifier

P9-17 = 5.0 PSI

P9-17 = 5.0 PSI

Add Drive Frequency Level

P9-09 = 59.0 Hz

P9-09 = 59.0 Hz

Add Drive Delay

P9-11 = 12.0 s

P9-11 = 12.0 s

<1> All other multiplexing and alternation parameters are set to default settings.

Duplex System with Jockey Pump Example

A customer requires a pump system with the following requirements:
• One small pump (the Jockey pump) will run the system during off-peak times.
• Two larger pumps will run the system when the demand is higher.
• The Jockey pump should not run when the two larger pumps are running.
• Pump wear is still an issue, but it is expected that the small pump will run longer hours and will always run first after a loss

of power.

• The feedback scale is 145 PSI.
• There is only one feedback transducer in the system.

(Jockey Pump)

10 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

Drive B

15 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

SYSTEM PRESSURE

FEEDBACK

Drive C

15 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

Figure 4.17 Simplified Wiring Diagram

Table 4.13 Related Parameters for Duplex System with Jockey Pump Example

Description

Jockey Pump

<1>

Drive B

<1>

Drive C

<1>

Node Address

H5-01 = 1

H5-01 = 2

H5-01 = 3

Highest Node Address

P9-25 = 3

P9-25 = 3

P9-25 = 3

4.7 iQpump Presets and Functions

116

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual