A.3 Drive Watt Loss Data

Table A.6 Watt Loss 200 V Class Single-Phase Models

Drive Model

Normal Duty (Swing PWM equal 2 kHz)

Rated Amps (A)

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

BV0006

6.0

30.1

19.4

49.5

BV0010

9.6

51.7

29.8

81.4

BV0012

12.0

61.3

37.1

98.4

BV0018

17.5

110.5

51.4

161.9

Table A.7 Watt Loss 200 V Class Three-Phase Models

Drive Model

Normal Duty (Swing PWM equal 2 kHz)

Rated Amps (A)

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

2V0006

6.0

27.5

17.2

44.7

2V0010

9.6

51.7

25.8

77.5

2V0012

12.0

61.3

30.4

91.7

2V0020

19.6

98.7

46.3

145.0

2V0030

30.0

246.4

88.9

335.3

2V0040

40.0

266.7

112.8

379.6

2V0056

56.0

357.9

151.8

509.7

2V0069

69.0

461.7

184.5

646.2

Table A.8 Watt Loss 400 V Class Three-Phase Models

Drive Model

Normal Duty (Swing PWM equal 2 kHz)

Rated Amps (A)

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

4V0002

2.1

18.5

13.9

32.4

4V0004

4.1

30.5

16.8

47.3

4V0005

5.4

44.5

21.8

66.3

4V0007

6.9

58.5

28.4

86.9

4V0009

8.8

63.7

31.4

95.1

4V0011

11.1

81.7

46.0

127.7

4V0018

17.5

181.2

80.1

261.3

4V0023

23.0

213.4

107.7

321.1

4V0031

31.0

287.5

146.1

433.6

4V0038

38.0

319.2

155.8

475.0

A.3 Drive Watt Loss Data