L6: torque detection – Yaskawa iQpump Micro User Manual

Page 258

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-52

(067C)

Pump Over Cycle Fault

Retry Selection

Pump Over Cycle

0: No retry

1: Retry

Determines whether the POC-Pump Over Cycle fault can be

auto-restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-53

(067D)

Volute-TStat Retry

Selection

Volute-TStat Flt

0: No retry

1: Retry

Determines whether the Volute T-Stat fault can be auto-

restarted.

0: No retry

1: Retry

Note:

The drive will restart only after the Volute-Tstat

digital input deactivates and the L5-04 timer

expires.

Default: 0

Range: 0, 1

u

L6: Torque Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L6-01

(04A1)

Torque Detection

Selection 1

Torq Det 1 Sel

0: Disabled

1: OL Alm at SpdAgr

2: OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

9: UL6Alm at SpdAgr

10: UL6Alm dur RUN

11: UL6Flt at SpdAgr

12: UL6Flt dur RUN

0: Disabled

1: oL3 detection only active during speed agree, operation

continues after detection

2: oL3 detection always active during run, operation continues

after detection

3: oL3 detection only active during speed agree, output shuts

down on an oL3 fault

4: oL3 detection always active during run, output shuts down

on an oL3 fault

5: UL3 detection only active during speed agree, operation

continues after detection

6: UL3 detection always active during run, operation continues

after detection

7: UL3 detection only active during speed agree, output shuts

down on an oL3 fault

8: UL3 detection always active during run, output shuts down

on an oL3 fault

9: UL6 Alarm at Speed Agree

10: UL6 Alarm during Run

11: UL6 Fault at Speed Agree

12: UL6 Fault during Run

Default: 0

Range: 0 to 12

L6-02

(04A2)

Torque Detection

Level 1

Torq Det 1 Lvl

Sets the overtorque and undertorque detection level.

Default: 15%

Min.: 0

Max.: 300

L6-03

(04A3)

Torque Detection

Time 1

Torq Det 1 Time

Sets the time an overtorque or undertorque condition must exist

to trigger torque detection 1.

Default: 10.0 s

Min.: 0.0

Max.: 10.0

L6-04

(04A4)

Torque Detection

Selection 2

Torq Det 2 Sel

0: Disabled

1: OL Alm at SpdAgr

2; OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

0: Disabled

1: oL4 detection only active during speed agree, operation

continues after detection

2: oL4 detection always active during run, operation continues

after detection

3: oL4 detection only active during speed agree, output shuts

down on an oL4 fault

4: oL4 detection always active during run, output shuts down

on an oL4 fault

5: UL4 detection only active during speed agree, operation

continues after detection

6: UL4 detection always active during run, operation continues

after detection

7: UL4 detection only active during speed agree, output shuts

down on an oL4 fault

8: UL4 detection always active during run, output shuts down

on an oL4 fault

Default: 0

Range: 0 to 8

L6-05

(04A5)

Torque Detection

Level 2

Torq Det 2 Lvl

Sets the overtorque and undertorque detection level.

Default: 150%

Min.: 0

Max.: 300

B.8 L: Protection Function

258

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual