The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation

when the Stop input S2 releases for 2 ms. When the digital input programmed for a forward/reverse operation is open, the

drive is set for forward operation. When the digital input is closed, the drive is set for reverse operation.

Note:

Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.

S1

S2

S5

SN

Run Command (Runs when Closed)

DRIVE

Stop Switch

(N.C.)

Run Switch

(N.O.)

Stop Command (Stops when Open)

FWD/REV (Multi-Function Input)

(H1-05 = 0)
Standard Digital Input Common

Figure 4.31 3-Wire Sequence Wiring Diagram

2 ms min.

Run command

OFF (stopped)

Can be either ON or OFF

OFF (forward)

Motor speed

Forward/reverse
command

Stop command

Stop

Reverse

Stop

Foward

TIME

Forward

ON (reverse)

Figure 4.32 3-Wire Sequence

Note:

1. The Run command must be closed for more than 2 ms.
2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate

that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive

power up.

WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying

power to the drive. Failure to comply could result in death or serious injury from moving equipment.

WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence

but set up for 2-Wire sequence (default). Make sure b1-17 is set to “0” (drive does not accept a Run command active at power up). When

initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.

Setting 2: External Reference 1/2 Selection

Switches between two different sources of Run Commands and Frequency References. When multi-function digital input

selection 2 (Ext Ref Sel) is programmed, the Run Command and Frequency Reference source can be switched between External

Reference 1 (b1-01/b1-02) and External Reference 2 (b1-15/b1-16) if the drive is in AUTO mode.

Settings 3 to 5: Multi-Step Speed Reference 1 to 3

Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs.

Setting 6: Jog Reference Selection

The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.

Setting 7: Accel/Decel Time Selection 1

Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04).

Refer to C1-01 to C1-04: Accel, Decel

Times 1 and 2 on page 128

for details.

Settings 8 and 9: Baseblock Command (N.O., N.C.)

When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm

flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs

Speed Search to restart the motor.