H3-09: terminal a2 signal level selection, H3-10: terminal a2 function selection – Yaskawa iQpump Micro User Manual

Page 150

Advertising
background image

100%

-100%

5 V

10 V

-5 V

-10 V

E1-04

E1-04

H3-01 = 0

H3-01 = 1

0 V

10 V

5 V

0 V

Gain = 200 %

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Gain = -200 %

Figure 4.55 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.

2.0 V

10 V

-6.0 V

-10 V

E1-04

0

-100%

-150%

2.0 V

10 V

100 %

Frequency
reference

-25%

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

H3-01 = 1

100%

Analog Input

Voltage

Analog Input

Voltage

Figure 4.56 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set DIP Switch S1-2 on the terminal board accordingly for a voltage input

or current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc.

Refer to Setting 0: 0 to 10 Vdc on page 149

.

Setting 1: 0 to 10 Vdc Bipolar

The input level is -10 to 10 Vdc.

Refer to Setting 1: 0 to 10 Vdc Bipolar on page 149

.

Setting 2: 4 to 20 mA

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 32

B

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.

4.8 Detailed iQpump Parameter Descriptions

150

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual