U5: pid monitors, U6: operation status monitors, U9: operation status monitors – Yaskawa iQpump Micro User Manual

Page 285

Advertising
background image

BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units.
2V0056 to 2V0069 and 4V0031 to 4V0038: 0.1 A units.

<4> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using

MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”

<5> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PID Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U5-01

(0057)

PID Feedback 1

PID Feedback 1

Displays the PID feedback value.

10 V: 100%

0.01%

<1>

U5-02

(0063)

PID Input

PID Input

Displays the amount of PID input (deviation between PID

setpoint and feedback).

10 V: 100%

0.01%

U5-03

(0064)

PID Output

PID Output

Displays PID control output.

10 V: 100%

0.01%

U5-04

(0065)

PID Setpoint

PID Setpoint

Displays the PID setpoint.

10 V: 100%

0.01%

<1>

U5-05

(07D2)

PID Differential

Feedback

PID Feedback 2

Displays the 2nd PID feedback value if differential feedback is

used (H3-oo = 16).

10 V: 100%

0.01%

U5-06

(07D3) PID Adjusted Feedback PID Diff Fdbk

Displays the difference of both feedback values if differential

feedback is used (U5-01 - U5-05). If differential feedback is not

used, then U5-01 and U5-06 will be the same.

10 V: 100%

0.01%

U5-99

(1599)

AUTO Setpoint

Auto Setpoint

Displays the PID Setpoint commanded by the source when the

drive is in AUTO Mode.

No signal output

available

0.01%

<1>

<1> Unit is determined by P1-02, System Units; scaling is determined by P1-03, Feedback Device Scaling; resolution is determined by b5-39, PID

System Units Display Digits.

u

U6: Operation Status Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U6-01

(0051)

Motor Secondary

Current (Iq)

Mot SEC Current

Displays the value of the motor secondary current (Iq). Motor

rated secondary current is 100%.

10 V: Motor

secondary rated

current

0.1%

u

U9: Operation Status Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U9-01

(1901)

Network PID Feedback Net PI Feedback

Displays the network PID feedback recognized by the iQpump

MEMOBUS network.

No signal output

available

Dep. on

P1-02

U9-02

(1902)

Network Activity

iQ Net Activity

Displays network traffic. A fluctuating number from 0 to 10000

denotes activity, while a relatively constant 0 denotes no

activity.

No signal output

available

<1>

U9-03

(1903)

Time to Alternate

Time to Alternate

Displays the time remaining before a drive requests the

alternation mode set in P9-04.

No signal output

available

min

U9-04

(1904)

Running Queue

Number

Running Queue No

Displays the position in the iQPump MEMOBUS Multiplex

running queue.

No signal output

available

<1> Unit changes based on network status.

<->: Drive cannot communicate to other drives
<+>: Drive is a node on a network
<M>: Drive is the master on an iQpump network.

B.15 U: Monitors

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

285

B

Parameter List