Control circuit wiring, Control circuit terminal block functions, 6 control circuit wiring – Yaskawa iQpump Micro User Manual

Page 75: Input terminals, Output terminals

Advertising
background image

3.6 Control Circuit Wiring

u

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S7), multi-function digital outputs

(MA, MB), multi-function pulse inputs and outputs (RP, MP) and multi-function photocoupler outputs (P1, P2). The default

is called out next to each terminal in

Figure 3.1

.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with

untested control circuits could result in death or serious injury.

WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter A1-06 may change the I/O

terminal function automatically from the factory setting. Failure to comply may result in death or serious injury.

n

Input Terminals

Table 3.8 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function

Digital Inputs

S1

Multi-function input 1 (Closed: Forward run, Open:

Stop)

Photocoupler

24 Vdc, 8 mA

Note: Drive preset to sinking mode. When using source mode, set

DIP switch S3 to allow for a 24 Vdc (±10%) external power supply.

Refer to Sinking/Sourcing Mode Switch on page 79

for details.

S2

Multi-function input 2 (Not used/Through mode)

S3

Multi-function input 3 (External pump fault (N.O.)

S4

Multi-function input 4 (Fault reset)

S5

Multi-function input 5 (Multi-step speed reference 1)

S6

Multi-function input 6 (HAND Mode)

S7

Multi-function input 7 (HAND Mode 2)

SC

Multi-function input common (Control common)

Sequence common

Safe Disable

Input

HC

Power supply for safe disable input

+24 Vdc (max 10 mA allowed)

H1

Safe disable input

Open: Output disabled

Closed: Normal operation

Note: Disconnect wire jumper between HC and H1 when using the

safe disable input. The wire length should not exceed 30 m.

Main

Frequency

Reference

Input

RP

Multi-function pulse train input (frequency reference)

Response frequency: 0.5 to 32 kHz

(Duty Cycle: 30 to 70%)

(High level voltage: 3.5 to 13.2 Vdc)

(Low level voltage: 0.0 to 0.8 Vdc)

(input impedance: 3 kΩ)

+V

Analog input power supply

+10.5 Vdc (max allowable current 20 mA)

A1

Multi-function analog input 1 (frequency reference)

Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000

A2

Multi-function analog input 2 (frequency reference)

Input voltage or input current (Selected by DIP switch S1 and H3-09)

0 to +10 Vdc (20 kΩ),

Resolution: 1/1000

4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),

Resolution: 1/500

AC

Frequency reference common

0 Vdc

n

Output Terminals

Table 3.9 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function Digital
Output

<1>

MA N.O. (Fault)

Digital output

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA (reference value)

MB N.C. (Fault)
MC Digital output common

Multi-Function

Photocoupler Output

P1

Photocoupler output 1 (During run)

Photocoupler output 48 Vdc, 2 to 50 mA

<2>

P2

Photocoupler output 2 (Fault)

PC

Photocoupler output common

Monitor Output

MP Pulse train output (Output frequency)

32 kHz (max)

<3>

<4>

AM Analog monitor output

0 to 10 Vdc (2 mA or less) Resolution: 1/1000

AC Monitor common

0 V

<1> Do not assign functions to digital relay outputs that involve frequent switching. This may shorten relay performance life. Switching life is estimated

at 200,000 times (assumes 1 A, resistive load).

3.6 Control Circuit Wiring

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

75

3

Electrical Installation

Advertising
This manual is related to the following products: