Yaskawa iQpump Micro User Manual

Page 269

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P4-03

(0CFC) Pre-Charge Time

Pre-Charge Time

Sets the time at which the drive will spend at the Pre-Charge

Frequency 1 during pre-charge. Maximum pre-charge time is

P4-03 + P4-07.

When P1-01 is set to 3 (MEMOBUS network), the function is

active only on the first drive to run in the network.

Setting this parameter to 0.0 disables the function.

Default: 0.0 min

Min.: 0.0

Max.: 3600.0

156

P4-05

(0CFE) Pre-Charge Loss of

Prime Level

Pre-Charge LOP

Detects loss of prime in the pump during Pre-charge 1.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P4-02, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<2>

Min.: 0.0

Max.: 1000.0

159

P4-06

(0CFF) Pre-Charge Frequency 2 Pre-Charge Freq2

Sets the frequency reference used when the Pre-Charge function

2 is active.

Setting this parameter to 0.0 disables the function.

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

159

P4-07

(0D00) Pre-Charge Time 2

Pre-Charge Time2

Sets the time at which the drive will spend at the Pre-Charge

frequency 2 during pre-charge. Maximum pre-charge time is

P4-03 + P4-07.

Default: 0.0 min

Min.: 0.0

Max.: 3600.0

159

P4-08

(0D01) Pre-Charge Loss of

Prime Level 2

Pre-Charge LOP 2

Detects loss of prime in the pump.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P4-06, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<2>

Min.: 0.0

Max.: 1000.0

159

P4-10

(0D03)

AUTO Mode Operator

Run Power Down

Storage

AMO PwDn-Storage

0: Disabled

1: Enabled

Stores the run status in AUTO Mode when operating from the

HOA keypad (b1-02 = 0).

0: Disabled

1: Enabled

WARNING! Sudden Movement Hazard. If the drive is

powered down while running, it will automatically initiate

an internal Run command upon power-up.

Default: 0

Range: 0, 1

159

P4-11

(0D04) Thrust Bearing

Acceleration Time

Thrust Acc. Time

Sets the time at which the drive output frequency will ramp up

to the reference frequency set in P4-12.

Default: 1.0 s

Min.: 0.0

Max.: 600.0

P4-12

(0D05) Thrust Bearing

Frequency

Thrust Freq.

The drive will accelerate to this frequency in the time set to

P4-11. The drive will decelerate from the frequency in the time

set to P4-13.

Default: 30.0 Hz

Min.: 0.0

Max.: [E1-04]

159

P4-13

(0D06) Thrust Bearing

Deceleration Time

Thrust Dec Time

Sets the amount of time it takes to bring the drive from the Thrust

Frequency set in P4-12 to stop when Thrust Mode is active.

When the Run command is removed while the drive is operating

in Thrust Mode above the Thrust Frequency, the time set in this

parameter is used when the frequency reference is at or below

the thrust frequency.

Default: 5.0 s

Min.: 0.0

Max.: 600.0

P4-17

(0D0A) Utility Start Delay

Utility Delay

Sets the amount of time that the drive will delay starting if a Run

command is present at power-up.

When P1-01, Pump Mode, is set to 3 (MEMOBUS network),

the drive is unavailable to the network (Pump Off Network)

when the function is active.

Setting this parameter to 0.0 disables the function.

Default: 0.2 min

Min.: 0.0

Max.: 1000.0

160

P4-21

(0D0E) Low City Input Select

Low City In Sel

0: Normally Open

1: Normally Closed

Selects the type of pressure switch connected to the “Low City

Press” digital input (H1-0o = 73).

0: Normally open (closed indicates the Low City Pressure

condition)

1: Normally closed (open indicates the Low City Pressure

condition)

Default: 1

Range: 0, 1

P4-22

(0D0F) Low City On-Delay

Time

Low City On Dly

Sets the amount of time a Low City Pressure condition needs to

be present before the drive will stop.

Default: 10 s

Min.: 1

Max.: 1000

P4-23

(0D10) Low City Off-Delay

Time

Low City Off Dly

Sets the amount of time a Low City Pressure condition needs to

be absent before the drive will restart.

Default: 5 s

Min.: 0

Max.: 1000

B.11 P: Pump Parameters

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

269

B

Parameter List

Advertising
This manual is related to the following products: