Setting AA: Utility Start Delay

Output terminal closes when the drive is stopped and waiting for the utility delay timer to expire. This setting is configured

by P4-17.

Settings 100 to 1AA: Functions 0 to AA with Inverse Output

These settings have the same function as settings 0 to AA but with inverse output. Set as 1oo, where the “1” indicates inverse

output and the last two digits specify the setting number of the function.
Examples:
• For inverse output of “8: During baseblock”, set 108.
• For inverse output of “4A: During KEB” set 14A.

n

H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1.

No.

Name

Setting Range

Default

H3-01

Terminal A1 Signal Level Selection

0, 1

0

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias

settings will be read as 0%.

Setting 1: 0 to 10 Vdc Bipolar

The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the

motor will rotate in reverse.

n

H3-02: Terminal A1 Function Selection

Selects the input signal level for analog input A1.

No.

Name

Setting Range

Default

H3-02

Terminal A1 Function Selection

0 to 41

0

n

H3-03, H3-04: Terminal A1 Gain and Bias Settings

Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.

No.

Name

Setting Range

Default

H3-03

Terminal A1 Gain Setting

-999.9 to 999.9%

100.0%

H3-04

Terminal A1 Bias Setting

-999.9 to 999.9%

0.0%

Setting Examples

• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since

the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04

above 5 Vdc.

4.8 Detailed iQpump Parameter Descriptions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

149