Yaskawa iQpump Micro User Manual

Page 249

Advertising
background image

H2-oo

Setting

Function

LCD Display

Description

Page

9

Frequency reference

source

Ref Source

Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or

b1-15).

Closed: Digital operator supplies the frequency reference.

–

A

HAND mode

Hand Mode

Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).

Closed: Pump is in HAND Mode operation.

–

B

Torque detection 1

(N.O.)

Trq Det 1 N.O.

Closed: An overtorque or undertorque situation has been detected.

–

C

Frequency reference

loss

Loss of Ref

Closed: Analog frequency reference has been lost.

Frequency reference loss is detected when the frequency reference drops below

10% of the reference within 400 ms.

–

D

Braking resistor fault

DB Overheat

Closed: Braking resistor or transistor is overheated or faulted out.

–

E

Fault

Fault

Closed: Fault occurred.

144

F

Through mode

Not Used

Set this value when using the terminal in the pass-through mode.

–

10

Minor fault

Minor Fault

Closed: An alarm has been triggered, or the IGBTs have reached 90% of their

expected life span.

–

11

Fault reset command

active

Reset Cmd Active

Closed: A command has been entered to clear a fault via the input terminals or

from the serial network.

–

12

Timer output

Timer Output

Closed: Timer output.

–

13

Speed agree 2

Fref/Fout Agree2

Closed: When drive output frequency equals the frequency reference ±L4-04.

–

14

User-set speed agree 2

Fref/Set Agree 2

Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.

–

15

Frequency detection 3

Freq Detect 3

Closed: When the drive output frequency is less than or equal to the value in L4-03

±L4-04.

–

16

Frequency detection 4

Freq Detect 4

Closed: When the output frequency is greater than or equal to the value in L4-03

±L4-04.

–

17

Torque detection 1

(N.C.)

Trq Det 1 N.C.

Open: Overtorque or undertorque has been detected.

–

18

Torque detection 2

(N.O.)

Trq Det 2 N.O.

Closed: Overtorque or undertorque has been detected.

19

Torque detection 2

(N.C.)

Trq Det 2 N.C.

Open: Overtorque or undertorque has been detected.

–

1A

During reverse

Reverse Dir

Closed: Drive is running in the reverse direction.

–

1B

During baseblock

(N.C.)

BaseBlk 2

Open: Drive has entered the baseblock state (no output voltage).

–

1E

Restart enabled

Dur Flt Restart

Closed: Automatic restart is performed

–

1F

Motor overload alarm

(oL1)

Overload (OL1)

Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers

this alarm.

–

20

Drive overheat pre-

alarm (oH)

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value.

–

22

Mechanical weakening

detection

MechFatigue(OL5)

Closed: Mechanical weakening detected.

–

2F

Maintenance period

Maintenance

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay

may require maintenance.

–

37

During frequency

output

During RUN 2

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial

Excitation is being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is

not being performed).

147

38

Drive enabled

Drive Enable

Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)

–

39

Watt hour pulse output Watt-hour Pulse

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

–

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

–

3E

PID feedback low

PID Feedback Low

Closed: PID feedback level is too low.

–

3F

PID feedback high

PID FeedbackHigh

Closed: The PID feedback level is too high.

–

4A

During KEB Ride-Thru During KEB

Closed: KEB Ride-Thru is being performed.

–

4C

During fast stop

During Fast Stop

Closed: A Fast Stop command has been entered from the operator or input

terminals.

–

4D

oH Pre-alarm time limit OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

–

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

249