Yaskawa iQpump Micro User Manual

Page 111

Advertising
background image

No.

Name

Description

Values

P9-99

Network Compatibility

Selection

Determines the communication compatibility for the iQPump MEMOBUS

network.

0: A-Ver: 30034

1: B-Ver: 30035/36

2: iQ Smart Network

Default: 2

Range: 0 to 2

n

Software (MEMOBUS) Multiplexing Setup

Wiring the Drive RS-485 Network Connections

R+ R- S+ S-

iQpump

RS-485 Network

Pump

R+ R- S+ S-

iQpump

Pump

R+ R- S+ S-

iQpump

Pump

R+ R- S+ S-

iQpump

Pump

Process Supply

Reservoir

Figure 4.13 System Overview

Perform the following steps to make the RS-485 network connections between all drives that will be multiplexed:

1.

Jumper terminals (R+ to S+) and jumper terminals (R- to S-) terminals on each individual drive according to

Figure

4.14

.

R+

S+

R-

S-

Drive X

Figure 4.14 Drive Terminal Jumpers

2.

Use shielded communication cable for steps 3 and 4 to connect the drives in a daisy chain manner according to

Figure 4.15

.

3.

Daisy chain the (R+ to S+) terminals between each drive.

4.

Daisy chain the (R- to S-) terminals between each drive.

4.7 iQpump Presets and Functions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

111

4

Start-Up Programming & Operation

Advertising
This manual is related to the following products: