Description

Jockey Pump

<1>

Drive B

<1>

Drive C

<1>

Pump Mode: 3 (Network)

P1-01 = 3

P1-01 = 3

P1-01 = 3

Feedback Source: 0 (Analog), 3

(Network)

P9-02 = 0

P9-02 = 3

P9-02 = 3

Lag Drive Speed: 0 (Always), 2

(Turn Off)

P9-05 = 2

P9-05 = 0

P9-05 = 0

Allow Net Run: 0 (Always), 2 (First

Only)

P9-20 = 2

P9-20 = 0

P9-20 = 0

Run Priority

P9-21 = 7

P9-21 = 8

P9-21 = 8

Lead Swap @ Sleep

P9-24 = 0

P9-24 = 1200 s

P9-24 = 1200 s

Setpoint

U5-99 = 100 PSI

U5-99 = 100 PSI

U5-99 = 100 PSI

Start Level

P1-04 = 80 PSI

P1-04 = 80 PSI

P1-04 = 80 PSI

<1> All other multiplexing and alternation parameters are set to default settings.

Triplex System Example

A customer who currently runs a duplex system would like to retrofit an existing triplex system with the following requirements:
• Three similarly sized pumps would run the system.
• A maximum of two drives should be running at any point; the third drive is a backup.
• Alternation should only happen when pumps are not running (sleeping).
• If one of the analog pressure feedback transducers should fail, read from a working one and notify the customer of the failure

by the alarm display.

• Setpoint is 90 PSI, feedback scale is 145 PSI, start level is 75 PSI.

Drive A

25 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

Drive B

25 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

SYSTEM PRESSURE

FEEDBACK

Drive C

25 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

SYSTEM PRESSURE

FEEDBACK

SYSTEM PRESSURE

FEEDBACK

Figure 4.18 Simplified Wiring Diagram

Table 4.14 Related Parameters for Triplex System Example

Description

Drive A

<1>

Drive B

<1>

Drive C

<1>

Node Address

H5-01 = 1

H5-01 = 2

H5-01 = 3

Highest Node Address

P9-25 = 3

P9-25 = 3

P9-25 = 3

Pump Mode: 3 (Network)

P1-01 = 3

P1-01 = 3

P1-01 = 3

Feedback Source: 2 (Analog ->Net,

with Alarm)

P9-02 = 2

P9-02 = 2

P9-02 = 2

Alternation Mode: 3 (FIFO @ Sleep)

P9-04 = 3

P9-04 = 3

P9-04 = 3

Maximum Running Pumps

P9-23 = 2

P9-23 = 2

P9-23 = 2

Setpoint

U5-99 = 90 PSI

U5-99 = 90 PSI

U5-99 = 90 PSI

Start Level

P1-04 = 75 PSI

P1-04 = 75 PSI

P1-04 = 75 PSI

<1> All other multiplexing and alternation parameters are set to default settings.

4.7 iQpump Presets and Functions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

117

4

Start-Up Programming & Operation