Drive derating data, Single-phase derating, A.4 drive derating data – Yaskawa iQpump Micro User Manual

Page 224: Single-phase input sizing

Advertising
background image

A.4 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Single-Phase Derating

iQpump Micro drives are compatible for use with both three-phase and single-phase input power supplies. The drive output

to the motor is always three-phase, regardless of number of input phases.
Output capacity to the motor is derated when using single-phase input power and the drive firmware includes protection for

single-phase input applications. This protection is enabled by default. Disabling this protection for single-phase input

applications can void warranty and result in premature failure.
Selection of larger models always results in greater output capacity to the motor when supplying the drive with three-phase

input power. However, the selection of larger models does not always yield greater output capacity when using the drive with

single-phase input power.
Several factors affect the amount of derated drive output capacity when single-phase input power is supplied to the drive:
• Single-phase input voltage level
• Motor voltage rating
• Amount of input impedance.
The tables in this section assist in model selection by considering factors that affect the amount of derating in single-phase

input power applications.

n

Single-Phase Input Sizing

The rated output current listed in the tables allows for a 120% overload for 60 seconds. Contact Yaskawa if assistance is needed

in selecting drive models with higher overload requirements. Adding more impedance than is specified will degrade

performance.

Table A.9 240 V Single-Phase Input (-5% to +10%)

Drive Model

Without Input Reactor

With Input Reactor

Rated Input

Current (A)

Rated

Output

Current (A)

Max

Applicable

Motor (HP)

Yaskawa Reactor Part

Number

Rated Input

Current (A)

Rated

Output

Current (A)

Max

Applicable

Motor (HP)

2V0006

7.3

4.9

1.0

URX000303

7.3

4.9

1.0

2V0010

10.8

6.8

1.5

URX000307

10.8

6.8

1.5

2V0012

13.9

7.5

2.0

URX000311

13.9

7.5

2.0

2V0020

24.0

9.7

2.0

URX000319

24.0

12.3

3.0

2V0030

37.0

7.5

2.0

URX000326

37.0

15.2

3.0

2V0040

52.0

16.7

5.0

URX000329

52.0

21.0

5.0

2V0056

68.0

23.4

5.0

URX000335

68.0

27.7

7.5

2V0069

80.0

25.8

7.5

URX000335

80.0

30.8

10.0

Table A.10 480 V Single-Phase Input (-5% to +10%)

Drive Model

Without Input Reactor

With Input Reactor

Rated Input

Current (A)

Rated

Output

Current (A)

Max

Applicable

Motor (HP)

Yaskawa Reactor Part

Number

Rated Input

Current (A)

Rated

Output

Current (A)

Max

Applicable

Motor (HP)

4V0002

2.1

1.3

0.5

URX000292

2.1

1.7

0.5

4V0004

4.3

2.4

1.0

URX000300

4.3

2.8

1.0

4V0005

5.9

3.5

1.5

URX000304

5.9

3.9

2.0

4V0007

8.1

3.5

1.5

URX000309

8.1

5.4

2.0

4V0009

9.4

5.1

2.0

URX000308

9.4

5.5

3.0

4V0011

14.0

5.5

3.0

URX000312

14.0

7.5

3.0

4V0018

20.0

4.5

2.0

URX000316

20.0

8.7

5.0

4V0023

24.0

5.5

3.0

URX000320

24.0

10.5

5.0

4V0031

38.0

7.9

3.0

URX000327

38.0

13.5

7.5

4V0038

44.0

11.3

5.0

URX000327

44.0

16.1

10.0

A.4 Drive Derating Data

224

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising
This manual is related to the following products: