B.3 C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions and

carrier frequency selections.

u

C1: Acceleration and Deceleration Times

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C1-01

(0200)

Acceleration Time 1

Accel Time 1

Sets the time to accelerate from 0 to maximum frequency.

Default: 20.0 s

Min.: 0.0
Max.: 6000.0

<1>

128

C1-02

(0201)

Deceleration Time 1

Decel Time 1

Sets the time to decelerate from maximum frequency to 0.

Default: 10.0 s

Min.: 0.0

Max.: 6000.0

<1>

128

C1-03

(0202)

Acceleration Time 2

Accel Time 2

Sets the time to accelerate from 0 to maximum frequency.

128

C1-04

(0203)

Deceleration Time 2

Decel Time 2

Sets the time to decelerate from maximum frequency to 0.

128

C1-09

(0208)

Fast Stop Time

Fast Stop Time

Sets the time for the Fast Stop function.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

C1-10

(0209)

Accel/Decel Time

Setting Units

Acc/Dec Units

0: 0.01 Seconds

1: 0.1 Seconds

0: 0.01 s (0.00 to 600.00 s)

1: 0.1 s (0.0 to 6000.0 s)

Default: 1

Range: 0, 1

C1-11

(020A)

Accel/Decel Time

Switching Frequency

Acc/Dec SW Freq

Sets the frequency to switch between accel/decel time settings. Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

C1-14

(0264)

Accel/Decel Rate

Frequency

Acc/DecRate Freq

Sets the base frequency used to calculate acceleration and

deceleration times.

When set to 0.0 Hz, the drive calculates the time required to

accelerate from 0 Hz to E1-04, and decelerate from E1-04 down

to 0 Hz (conventional setting).

When set to any other value above 0.0 Hz, the drive calculates

the time required to accelerate from 0 Hz to C1-14, and to

decelerate from C1-14 down to 0 Hz.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

<1> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range

becomes 0.00 to 600.00 seconds.

u

C2: S-Curve Characteristics

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C2-01

(020B)

S-Curve Characteristic

at Accel Start

SCrv Acc @ Start

The S-curve can be controlled at the four points shown below.

Run Command

Time

Output Frequency

C2-01

C2-04

C2-02

C2-03

ON

OFF

Default: 0.20 s

Min.: 0.00

Max.: 10.00

C2-02

(020C)

S-Curve Characteristic

at Accel End

SCrv Acc @ End

Default: 0.20 s

Min.: 0.00

Max.: 10.00

C2-03

(020D)

S-Curve Characteristic

at Decel Start

SCrv Dec @ Start

Default: 0.20 s

Min.: 0.00

Max.: 10.00

C2-04

(020E)

S-Curve Characteristic

at Decel End

SCrv Dec @ End

Default: 0.00 s

Min.: 0.00

Max.: 10.00

B.3 C: Tuning

234

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual