Input programmed for 76 will decrease the bias, Table 4.21 – Yaskawa iQpump Micro User Manual

Page 138

Advertising
background image

Table 4.21 Up/Down 2 Operations

Condition

Freq. Ref.

Source

d4-03

d4-05

d4-01

Operation

Frequency Saved

1

Multi-Step Speed

Reference

0

0

0

• Accelerates (increases the bias) while the Up 2

terminal is closed.

• Decelerates (decreases the bias) while Down 2 is

closed.

• Holds output frequency (holds the bias) when no

Up 2 or Down 2 input or both active.

• Resets the bias when the reference changes.
• Operates with the frequency reference in all other

situations.

Not saved

2

1

If the bias and frequency reference

are constant for 5 s, the bias is

added to the active frequency

reference and reset afterwards.

3

1

--

• Accelerates (increases the bias) while the Up 2

terminal is closed.

• Decelerates (decreases the bias) while Down 2 is

closed.

• Otherwise operates at the frequency reference.

Not saved

4

Multi-Step Speed

Reference

Value

other

than 0

--

0

• When the Up 2 is enabled, the drive accelerates to

the frequency reference plus d4-03 (bias is

increased for d4-03).

• When Down 2 is enabled, the drive decelerates to

the frequency reference minus d4-03 (bias is

decreased for d4-03).

• Holds output frequency (holds the bias) when

neither Up/Down 2 inputs are active or both inputs

are active.

• Resets the bias when the reference changes.
• Operates with the frequency reference in all other

situations.

Not saved

5

1

If the bias and frequency reference

are constant for 5 s, the bias is

added to the active frequency

reference and reset afterwards.

6

Other (analog

comm., etc.)

0

0

0

• Accelerates (increases the bias) while the Up 2

terminal is closed.

• Decelerates (decreases the bias) while Down 2 is

closed.

• Holds output frequency (holds the bias) when

neither Up/Down 2 inputs are active or both inputs

are active.

• If the frequency reference changes for more than

the time set to d4-07 during accel/decel, bias value

is held until the output frequency meets the

reference (speed agree).

Not saved

7

1

If the bias is constant for 5 s, it is

saved to parameter d4-06. The

frequency reference cannot be

overwritten, so only the bias is

saved.

8

Other (analog

comm, etc.)

0

1

--

• Accelerates (increases the bias) while the Up 2

terminal is closed.

• Decelerates (decreases the bias) while Down 2 is

closed.

• Otherwise operates at the frequency reference

Not saved

9

Value

other

than 0

--

0

• When Up 2 is enabled, drive accelerates to the

frequency reference plus d4-03 (increases the bias

for d4-03).

• When Down 2 is enabled, drive decelerates to the

frequency reference minus d4-03 (decreases the

bias for d4-03).

• If the frequency reference changes for more than

d4-07 during accel/decel, bias value is held until the

output frequency meets the reference (speed agree).

Not saved

10

1

If the bias is constant for 5 s, it is

saved to parameter d4-06. The

frequency reference cannot be

overwritten, so only the bias is

saved.

Settings 7A and 7B: KEB Ride-Thru 2 (N.C., N.O.)

An input terminal set to 7A or 7B can trigger Single Drive KEB Ride-Thru during deceleration. L2-29 is disregarded if this

is enabled.

Digital Input Function

Drive Operation

Input Open

Input Closed

Setting 7A (N.C.)

Single Drive KEB Ride-Thru 2

Normal operation

Setting 7B (N.O.)

Normal operation

Single Drive KEB Ride-Thru 2

Note:

Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.

4.8 Detailed iQpump Parameter Descriptions

138

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising
This manual is related to the following products: