Digital Input Function

Drive Operation

Input Open

Input Closed

Setting 8 (N.C.)

Baseblock (Interrupt output)

Normal operation

Setting 9 (N.O.)

Normal operation

Baseblock (Interrupt output)

WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when

the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load

from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.

Begin Speed Search from the
previous frequency reference

Run command

Baseblock input

Frequency
reference

Output frequency

OFF

ON

Output off, motor coasts

ON

Baseblock

release

Figure 4.33 Baseblock Operation During Run

Setting A: Accel/Decel Ramp Hold

When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.

Acceleration or deceleration resumes when the input is reopened.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive saves the output frequency to memory when the Ramp

Hold input is closed. When the drive is restarted after stop or after power supply interruption, the saved output frequency

becomes the frequency reference (provided that the Accel/decel ramp hold input is still closed).

Setting B: Drive Overheat Alarm (oH2)

Triggers an oH2 alarm when the contact closes. Drive operation is not affected because this is an alarm.

Setting C: Analog Terminal Input Selection (Terminal A1, A2)

When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog

terminals.

Setting F: Not Used/Through Mode

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in

the drive. Setting F, however, still allows the input status of the terminal (open or closed) to be read out by a PLC via a

communication option or MEMOBUS/Modbus communications. The drive input terminals can then be used as remote I/O by

the PLC.

Settings 10 and 11: Up/Down Function

The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed

as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input

(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the digital operator, the analog inputs, and the pulse

input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in

Table 4.19

:

Table 4.19 Up, Down Command

Status

Drive Operation

Up (10)

Down (11)

Open

Open

Hold current frequency reference

Closed

Open

Increase frequency reference

4.8 Detailed iQpump Parameter Descriptions