Yaskawa iQpump Micro User Manual

Page 160

Advertising
background image

At start, the drive will use the P4-11 acceleration time until the P4-12 frequency is reached, at which time it will use the active

C1-oo acceleration and deceleration times. At stop, if the output frequency is above the P4-12 setting, the active C1-oo

deceleration time will be used until the P4-12 setting is reached at which time it will use the P4-13 time setting for the rest of

deceleration.
If P4-12 is set greater than P1-06 (minimum Pump Speed), P4-12 will become the frequency lower limit. The drive PID control

must be disabled (b5-01 = 0) for this function to work.

No.

Parameter Name

Setting Range

Default

P4-12

Thrust Bearing Frequency

0.0 to E1-04

30.0 Hz

P4-11

Output
frequency

“Thruse Active”
Message &
Digital Output
(H2-0

☐ = A9)

Run
command

C1-01

(or selected)

Accel Rate

P4-12 Thrust Frequency

P4-13

Thrust Bearing

Ramp to Stop (b1-03 = 0)

C1-02

(or selected)

Decel Rate

Figure 4.64 Thrust Bearing

n

P4-13: Thrust Bearing Deceleration Time

Specifies the amount of time that the drive will decelerate from the value set in P4-12 until reaching 0.

No.

Name

Setting Range

Default

P4-13

Thrust Bearing Deceleration Time

0.0 to 600.0 s

5.0 s

While this parameter is active, the drive will display the message “Thrust Mode – Thrust Active” on the keypad and the digital

output associated with thrust mode (H2-0o = A9) will close. For output frequencies above P4-12, the drive standard

deceleration rates apply and the message and digital output will clear. When this parameter is set to 0.0, the drive will use the

standard deceleration rate.

n

P4-17: Utility Start Delay

Sets the delay time after power up until the drive will recognize a Run command present within one second of power up or

when the Run command is jumpered on the terminal strip.
This is useful in preventing a peak power surge when multiple drives power up and begin accelerating simultaneously. This

function works when the drives all have different P4-17 settings to spread out the power draw during acceleration.
If the Run command is removed and re-applied during the P4-17 time, the drive will cancel the utility start delay and

immediately begin running.
The Utility Start Delay is applied when the drive is auto-restarting after an Undervoltage (Uv) or an Overvoltage (ov) condition.

No.

Parameter Name

Setting Range

Default

P4-17

Utility Start Delay

0.0 to 1000.0 min

0.2 min

n

P4-32: Pre-Charge Level 2

For normal PI operation during Pre-charge 2, if the PI Feedback signal rises above the P4-32 level, Pre-charge 2 is cancelled

and the drive resumes normal operation.
For inverse PI operation and during Pre-charge 2, if the PI Feedback signal goes below the P4-32 level, Pre-charge 2 is cancelled

and the drive resumes normal operation.
When set to zero, Pre-charge 2 still runs when P4-07 is set, but uses P4-01 to determine if normal operation should resume.

No.

Name

Setting Range

Default

P4-32

Pre-Charge Level 2

0.0 to 6000.0

0.0

4.8 Detailed iQpump Parameter Descriptions

160

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual