Yaskawa iQpump Micro User Manual

Page 247

Advertising
background image

H1-oo

Setting

Function

LCD Display

Description

Page

66

KEB Ride-Thru 1

(N.O.)

KEB Ridethru NO

Closed: KEB Ride-Thru 1 enabled.

67

Communications test

mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the

test completes successfully.

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

73

Low City Press

Low City Press

Indicates that sufficient or insufficient pressure is present on the inlet to the pump.

Used mainly for pressure booster situations.

Note:

1. Parameter P4-21 determines if this input is normally open or

normally closed.

2. When P1-01 = 3, an alarm condition will cause drives in the

network to stop running and show a “Net Pump Err” message.

75

Up 2 command

Up Command 2

Controls the bias added to the frequency reference by the Up/Down 2 function.

The Up 2 and Down 2 commands must always be used in conjunction with one

another.

76

Down 2 command

Down Command 2

Controls the bias added to the frequency reference by the Up/Down 2 function.

The Up 2 and Down 2 commands must always be used in conjunction with one

another.

7A

KEB Ride-Thru 2 (N.C.) KEB Ridethru2NC

Open: KEB Ride-Thru 2 enabled.

7B

KEB Ride-Thru 2

(N.O.)

KEB Ridethru2NO

Closed: KEB Ride-Thru 2 enabled.

80

HAND Mode

Hand Mode

Closed: HAND Mode operation. Frequency reference determined by P5-01 and

P5-02.

Open: Stop Mode when no Run command.

139

81

HAND Mode 2

Hand Mode 2

Closed: HAND Mode operation. Frequency reference determined by P5-05.

Open: Stop Mode when no Run command.

139

83

Alternate Multi Setpoint

(Q1-02)

AltMultiSP Q1-02

Closed: Q1-02 becomes the PID setpoint

84

Alternate Multi Setpoint

(Q1-03)

AltMultiSP Q1-03

Closed: Q1-03 becomes the PID setpoint

85

Alternate Multi Setpoint

(Q1-04)

AltMultiSP Q1-04

Closed: Q1-04 becomes the PID setpoint

88

Volute-Thermostat

Normally Open

Volute-TStat NO

Function active when the drive is running.

Closed: Drive will trip on “VLTS - Volute-TStat Flt”

Open: Thermostat fault not active

Note:

Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -

Volute-TStat Flt”.

89

Volute-Thermostat

Normally Closed

Volute-TStat NC

Function active when the drive is running.

Closed: Thermostat fault not active

Open: Drive will trip on “VLTS - Volute-TStat Flt”

Note:

Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -

Volute-TStat Flt”.

8C

Disable Pre-Charge

Disable Pre-Chrg

Closed: Pre-Charge disabled.

8D

Multi Setpoint 1

Multi Setpoint 1

Open: Frequency reference, Q1-01, or Q1-03 is PID Setpoint.

Closed: Q1-02 or Q1-04 is PID Setpoint.

139

8E

Multi Setpoint 2

Multi Setpoint 2

Open: Frequency reference, Q1-01, or Q1-02 is PID Setpoint.

Closed: Q1-03 or Q1-04 is PID Setpoint.

8F

Low Water Level

Low Water

Function active in AUTO Mode during normal operation, also used with Pre-

Charge function. Function logic depends on P1-30, Low Water Digital Input

Configuration.

P1-30 = 0 (Normally open)

Closed: Low water level fault

Open: Reservoir/Tank is filled to normal level

P1-30 = 1 (Normally closed)

Closed: Reservoir/Tank is filled to normal level

Open: Low water level fault

Pre-Charge function: Function uses the low water level input as “Tank/Reservoir”

feedback to indicate that the water level has been reached.

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

247

B

Parameter List