H1-oo

Setting

Function

LCD Display

Description

Page

66

KEB Ride-Thru 1

(N.O.)

KEB Ridethru NO

Closed: KEB Ride-Thru 1 enabled.

–

67

Communications test

mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the

test completes successfully.

–

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

–

73

Low City Press

Low City Press

Indicates that sufficient or insufficient pressure is present on the inlet to the pump.

Used mainly for pressure booster situations.

Note:

1. Parameter P4-21 determines if this input is normally open or

normally closed.

2. When P1-01 = 3, an alarm condition will cause drives in the

network to stop running and show a “Net Pump Err” message.

–

75

Up 2 command

Up Command 2

Controls the bias added to the frequency reference by the Up/Down 2 function.

The Up 2 and Down 2 commands must always be used in conjunction with one

another.

–

76

Down 2 command

Down Command 2

Controls the bias added to the frequency reference by the Up/Down 2 function.

The Up 2 and Down 2 commands must always be used in conjunction with one

another.

–

7A

KEB Ride-Thru 2 (N.C.) KEB Ridethru2NC

Open: KEB Ride-Thru 2 enabled.

–

7B

KEB Ride-Thru 2

(N.O.)

KEB Ridethru2NO

Closed: KEB Ride-Thru 2 enabled.

–

80

HAND Mode

Hand Mode

Closed: HAND Mode operation. Frequency reference determined by P5-01 and

P5-02.

Open: Stop Mode when no Run command.

139

81

HAND Mode 2

Hand Mode 2

Closed: HAND Mode operation. Frequency reference determined by P5-05.

Open: Stop Mode when no Run command.

139

83

Alternate Multi Setpoint

(Q1-02)

AltMultiSP Q1-02

Closed: Q1-02 becomes the PID setpoint

–

84

Alternate Multi Setpoint

(Q1-03)

AltMultiSP Q1-03

Closed: Q1-03 becomes the PID setpoint

–

85

Alternate Multi Setpoint

(Q1-04)

AltMultiSP Q1-04

Closed: Q1-04 becomes the PID setpoint

–

88

Volute-Thermostat

Normally Open

Volute-TStat NO

Function active when the drive is running.

Closed: Drive will trip on “VLTS - Volute-TStat Flt”

Open: Thermostat fault not active

Note:

Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -

Volute-TStat Flt”.

–

89

Volute-Thermostat

Normally Closed

Volute-TStat NC

Function active when the drive is running.

Closed: Thermostat fault not active

Open: Drive will trip on “VLTS - Volute-TStat Flt”

Note:

Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -

Volute-TStat Flt”.

–

8C

Disable Pre-Charge

Disable Pre-Chrg

Closed: Pre-Charge disabled.

–

8D

Multi Setpoint 1

Multi Setpoint 1

Open: Frequency reference, Q1-01, or Q1-03 is PID Setpoint.

Closed: Q1-02 or Q1-04 is PID Setpoint.

139

8E

Multi Setpoint 2

Multi Setpoint 2

Open: Frequency reference, Q1-01, or Q1-02 is PID Setpoint.

Closed: Q1-03 or Q1-04 is PID Setpoint.

–

8F

Low Water Level

Low Water

Function active in AUTO Mode during normal operation, also used with Pre-

Charge function. Function logic depends on P1-30, Low Water Digital Input

Configuration.

P1-30 = 0 (Normally open)

Closed: Low water level fault

Open: Reservoir/Tank is filled to normal level

P1-30 = 1 (Normally closed)

Closed: Reservoir/Tank is filled to normal level

Open: Low water level fault

Pre-Charge function: Function uses the low water level input as “Tank/Reservoir”

feedback to indicate that the water level has been reached.

–

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

247

B

Parameter List