Terminal configuration, Serial communication terminals, 6 control circuit wiring – Yaskawa iQpump Micro User Manual

Page 76

Advertising
background image

<2> Connect a suppression diode as shown in

Figure 3.18

when driving a reactive load such as a relay coil. Ensure the diode rating is greater than the

circuit voltage.

<3> When set for sourcing. +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher.
<4> When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.

A

B

C

D

A – External power, 48 V max.
B – Suppression diode

C – Coil
D – 50 mA or less

Figure 3.18 Connecting a Suppression Diode

n

Serial Communication Terminals

Table 3.10 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus

Communication

R+

Communications input (+)

MEMOBUS/Modbus communication: Use a

RS-485 or RS-422 cable to connect the drive.

RS-485/422

MEMOBUS/

Modbus

communication

protocol 115.2 kbps

(max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

u

Terminal Configuration

S1

S2

S3

S4

S5

S6

S7 HC SC H1 RP

R+ R–

S+ S–

IG

P1

P2 PC A1

A2

+V AC AM AC MP

MC

MB

MA

S1

S2

S3

S4

S5

S6

S7 HC SC H1 RP

R+ R-

S+ S-

IG

P1

P2 PC A1

A2

+V AC AM AC MP

MC

MB

MA

Figure 3.19 Removable Control Circuit Terminal Block

3.6 Control Circuit Wiring

76