The digital output programmed to “High Feedback” (H2-0o= 96) closes. The drive will also display the “High Feedback –

High FB Sensed” alarm. The digital output will remain closed until the fault is reset.

Setting 1: Alarm

When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”

(H2-0o= 96) closes and the drive displays the “High Feedback – High FB Sensed” alarm.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high

feedback detection are no longer true, the digital output will open and the alarm will clear.

Setting 2: Digital out only

When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”

(H2-0o= 96) closes.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high

feedback detection are no longer true, the digital output will open.

n

P2-01: Sleep Level Type

Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-

dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents

a low-activity condition for the system.

Note:

Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.

No.

Parameter Name

Setting Range

Default

P2-01

Sleep Level Type

0 to 3

0

Setting 0: Output frequency
Setting 1: Output current
Setting 2: Feedback
Setting 3: Output speed (RPM)

n

P2-02: Sleep Level

Sets the level at which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls below

the P2-02 setting for the time set in P2-03.

No.

Parameter Name

Setting Range

Default

P2-02

Sleep Level

0.0 to 6000.0

0.0 Hz

n

P2-03: Sleep Delay Time

Sets the delay time after which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls

below the P2-02 setting for the time set in P2-03.

No.

Parameter Name

Setting Range

Default

P2-03

Sleep Delay Time

0 to 3600 s

5 s

n

P4-01: Pre-Charge Level

Sets the level at which the drive will activate the pre-charge function. At start, if the PID is below the P4-01 setting, the drive

will run at the P4-02 frequency setting for the time set in P4-03. PID control is delayed until the Pre-charge function stops.

The drive will exit the pre-charge function early if the feedback rises above the P4-01 setting or if a Low Water digital input

switch (H1-oo = 8F) deactivates. Pre-charge is useful to slowly fill or pressurize a system.

No.

Parameter Name

Setting Range

Default

P4-01

Pre-Charge Level

0.0 to 6000.0

0.0 PSI

n

P4-02: Pre-Charge Frequency

Sets the frequency at which the pre-charge function will run.

No.

Parameter Name

Setting Range

Default

P4-02

Pre-Charge Frequency

0.0 to E1-04

0.0 Hz

4.8 Detailed iQpump Parameter Descriptions