Yaskawa iQpump Micro User Manual

Page 284

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-10

(005C) kWh, Lower 4 Digits

kWh Lower 4 dig

Monitors the drive output power usage (or consumption). The

value is shown as a 9-digit number displayed across two monitor

parameters, U4-10 and U4-11.

Example:

12345678.9 kWh is displayed as:

U4-10: 678.9 kWh

U4-11: 12345 MWh

No signal output

available

1 kWh

U4-11

(005D) kWh, Upper 5 Digits

kWh Upper 5 dig

No signal output

available

1 MWh

U4-13

(07CF) Peak Hold Current

Current PeakHold

Displays the highest current value that occurred during run.

No signal output

available

0.01 A

<3> <4>

<5>

U4-14

(07D0)

Peak Hold Output

Frequency

Freq@ I PeakHold

Displays the output frequency when the current value shown in

U4-13 occurred.

No signal output

available

0.01 Hz

U4-16

(07D8)

Motor Overload

Estimate (oL1)

Motor OL1 Level

Shows the value of the motor overload detection accumulator.

100% is equal to the oL1 detection level.

10 V: 100%

0.1%

U4-18

(07DA)

Frequency Reference

Source Selection

Reference Source

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

1 = Reference 1 (b1-01)

2 = Reference 2 (b1-15)

Y-nn: indicates the reference source

0-01 = Digital operator

1-00 = Analog

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

1-03 = Analog (terminal A3)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

5-01 = Pulse input

9-01 = Up/Down Command

No signal output

available

U4-19

(07DB)

Frequency Reference

from MEMOBUS/

Modbus Comm.

MEMOBUS Freq Ref

Displays the frequency reference provided by MEMOBUS/

Modbus (decimal).

No signal output

available

0.01%

U4-20

(07DC)

Option Frequency

Reference

Option Freq Ref

Displays the frequency reference input by an option card

(decimal).

No signal output

available

U4-21

(07DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

1 = Reference 1 (b1-02)

Y: Input power supply data

0 = Digital operator

1 = External terminals

3 = MEMOBUS/Modbus communications

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, digital operator)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

10: Run command was switched on while copying parameters

12: Clock is being set for RTC

No signal output

available

U4-22

(07DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(07DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

<1> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<2> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
<3> Display is in the following units:

B.15 U: Monitors

284

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual