3.8 Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input. For voltage signals both analog inputs, A1 and

A2, can be used, for current signals A2 must be used.
When using input A2 as a voltage input, set DIP switch S1 to “V” (left position) and program parameter H3-09 to 0 (0 to +10

Vdc with lower limit) or 1 (0 to +10 Vdc without lower limit).
To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and set parameter H3-09 = 2 or 3 (4-20 mA

or 0-20 mA). Set parameter H3-10 = 0 (frequency reference).

Note:

If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both input values builds the frequency

reference.

Table 3.14 Frequency Reference Configurations

Voltage Input

Current Input

Drive

Main speed

frequency reference

(voltage input)

Main speed

frequency reference

(current input)

Frequency reference

common

+10.5 V

20 mA current

0 to 10 V

+V

A1

A2

AC

Drive

Main speed

frequency reference

(voltage input)
Main speed

frequency reference

(current input)

Frequency reference

common

4 to 20 mA input
or
0 to 20 mA input

+10.5 V

20 mA current

+V

A1

A2

AC

V

I

Figure 3.27 DIP Switch S1

Table 3.15 DIP Switch S1 Settings

Setting Value

Description

V (left position)

Voltage input (0 to 10 V)

I (right position)

Current input (4 to 20 mA or 0 to 20 mA): default setting

Table 3.16 Parameter H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-09

Frequency ref. (current)

terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to +10 V, unipolar input (with lower limit)

1: 0 to +10 V, bipolar input (no lower limit)

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2