Lead: setpoint, Lag: fixed hold, Lag: fixed p9-06 – Yaskawa iQpump Micro User Manual

Page 114: Lag: follow lead

Advertising
background image

Network State

Display

Drive is in AUTO Mode, Lead operation and

is currently regulating the system using PID

control.

Lead: Setpoint

- MODE -

DRV RDY

Home

U1-02=

U1-91=

52.38Hz

62.8PSI

U5-99= 100.0

PSI

Drive is in AUTO Mode, Lag operation and

is holding the speed at the time it made the

switch from being a lead drive to a lag. Speed

is held until P9-07 time expires. The Home

screen will display U1-01 instead of U5-99.

Lag: Fixed Hold

- MODE -

DRV RDY

Home

U1-02=

U1-91=

59.41Hz

99.8PSI

U1-01= 59.41

HZ

Drive is in AUTO Mode, Lag operation and

is running at the speed set in P9-06. The

Home Screen will display U1-01 instead of

U5-99.

Lag: Fixed P9-06

- MODE -

DRV RDY

Home

U1-02=

U1-91=

55.00Hz

99.9PSI

U1-01= 55.00

HZ

Drive is in AUTO Mode, Lag operation and

is following the speed of the current Lead

drive. The Home screen will display U1-01

instead of U5-99.

Lag: Follow Lead

- MODE -

DRV RDY

Home

U1-02=

U1-91=

51.35Hz

98.9PSI

U1-01= 51.37

HZ

PID Feedback via Network

The Network PID Feedback comes from a drive on the network with a valid analog PID feedback source and can be used as

the primary or secondary feedback source for a networked drive.
Set P9-02 to 0 if a drive has an analog PID feedback device installed and switching to network as a backup is not desired.
If a drive has an analog PID feedback device installed and the network PID feedback is considered as a backup, set P9-02 to

1 for no alarm message when switched and set P9-02 to 2 for an alarm.
Set P9-02 to 3 if a drive has no analog PID feedback device installed and relies solely on the analog PID feedback of another

networked drive.

Note:

Connect an analog PID feedback device to each drive for best performance.

Related Parameters

No.

Parameter Name

Setting Values

H5-01

Drive Node Address

Default: 1F (Hex)

Min.: 0

Max.: FF

P1-01

Pump Mode

Default: 0

Range: 0, 3

P9-02

Feedback Source

Default: 0

Range: 0 to 3

P9-25

Highest Node Address

Default: 4

Range: 2 to 4

4.7 iQpump Presets and Functions

114