Yaskawa iQpump Micro User Manual

Page 188

Advertising
background image

Digital Operator Display

Minor Fault Name

A general-purpose motor is driven below

the rated speed with a high load

• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor

specifically designed to operate in the desired speed range.

The output voltage is too high

• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.

The wrong motor rated current is set to

E2-01

• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.

The base frequency is set incorrectly

• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).

The electrical thermal protection

characteristics and motor overload

characteristics do not match

• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.

The electrical thermal relay is operating at

the wrong level

• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).

Motor overheated by overexcitation

operation

• Overexcitation increases the motor loss and the motor temperature. Excessive duration of overexcitation

may cause motor damage. Prevent excessive overexcitation operation or apply proper cooling to the motor.

• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.

Parameters related to Speed Search are set

incorrectly

• Check values set to Speed Search related parameters.
• Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.

Output current fluctuation due to power

supply loss

Check the power supply for phase loss.

Digital Operator Display

Minor Fault Name

oL2

Drive Overload
The thermal sensor of the drive triggered overload protection.

Cause

Possible Solution

Load is too heavy

Reduce the load.

Acceleration or deceleration time is too

short

Increase the settings for the acceleration and deceleration times (C1-01 through C1-04).

The output voltage is too high

• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.

Drive capacity is too small

Replace the drive with a larger model.

Overload occurred when operating at low

speeds

• Reduce the load when operating at low speeds.
• Replace the drive with a model that is one frame size larger.
• Lower the carrier frequency (C6-02).

Excessive torque compensation

Reduce the torque compensation gain in parameter C4-01 until there is less current but no speed loss.

Parameters related to Speed Search are set

incorrectly

• Check the settings for all Speed Search related parameters.
• Adjust the current used during Speed Search (b3-03) and the Speed Search deceleration time (b3-02).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.

Output current fluctuation due to input

phase loss

Check the power supply for phase loss.

Digital Operator Display

Minor Fault Name

oL3

Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check L6-02 and L6-03 settings.

Fault on the machine side (e.g., machine is

locked up)

Check the status of the load. Remove the cause of the fault.

5.3 Alarm Detection

188

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising
This manual is related to the following products: