n

P1-10: Low Feedback Selection

Selects the drive response to a Low Feedback condition. When the PID feedback falls below the P1-08 setting for the time set

in P1-09, the drive will respond based on the setting in P1-10.

No.

Parameter Name

Setting Range

Default

P1-10

Low Feedback Selection

0 to 2

0

Low feedback detection is enabled when:
• P1-08 > 0.0
• Drive is running in AUTO Mode, including sleep boost and feedback drop detection (standard PID, b5-09 = 0)
• Run Command is present (including sleep and timer operation) (inverse PID, b5-09 = 1)

Setting 0: Fault

When feedback drops below the P1-08 level for longer than the time set in P1-09, the drive will fault on the “LFB – Low

Feedback” fault and coast to a stop.
The digital output programmed to “Low Feedback” (H2-0o = 97) closes. The drive will also display the “Low Feedback –

Low FB Sensed” alarm. The digital output will remain closed until the fault is reset.

Setting 1: Alarm

When feedback drops below the P1-08 level for longer than the time set in P1-09, the digital output programmed to “Low

Feedback” (H2-0o = 97) closes and the drive displays the “Low Feedback – Low FB Sensed” alarm.
When feedback rises above the level determined by P1-08 and P1-14, or when one or more of the conditions that enable low

feedback detection are no longer true, the digital output will open and the alarm will clear.

Setting 2: Digital out only

When feedback drops below the P1-08 level for longer than the time set in P1-09, the digital output programmed to “Low

Feedback” (H2-0o = 97) closes.
When feedback rises above the level determined by P1-08 and P1-14, or when one or more of the conditions that enable low

feedback detection are no longer true, the digital output will open.

n

P1-11: High Feedback Level

Sets the level at which a High Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting for

the time set in P1-12, the drive will respond based on the setting in P1-13.

No.

Parameter Name

Setting Range

Default

P1-11

High Feedback Level

0.0 to 6000.0

155.0 PSI

n

P1-12: High Feedback Level Fault Delay Time

Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting

for the time set in P1-12, the drive will respond based on the setting in P1-13.

No.

Parameter Name

Setting Range

Default

P1-12

High Feedback Level Fault Delay Time

0 to 3600 s

5 s

n

P1-13: High Feedback Selection

Selects the drive response to a High Feedback condition. When the PID feedback rises above the P1-11 setting for the time

set in P1-12, the drive will respond based on the setting in P1-13.

No.

Parameter Name

Setting Range

Default

P1-13

High Feedback Selection

0 to 2

0

High feedback detection is enabled when:
• P1-11 > 0
• Run Command present, including sleep & timer operation (standard PID, b5-09 = 0)
• Drive is running in AUTO Mode, including feedback drop detection (inverse PID, b5-09 = 1).

Setting 0: Fault

When feedback rises above the P1-11 for longer than the time set in P1-12, the drive will fault on the “HFB – High Feedback”

fault and coast to a stop.

4.8 Detailed iQpump Parameter Descriptions

154

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual