n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

No.

Name

Setting Range

Default

L5-04

Fault Reset Interval Time

10.0 to 3600.0 s

20.0 s

n

o1-08: Third Line User Monitor Selection

Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set “403” to display

monitor parameter U4-03.

No.

Name

Setting Range

Default

o1-08

Second Line User Monitor Selection

101 to 904

191

n

P1-01: Pump Mode

Selects the base operation mode of the drive controller.

No.

Parameter Name

Setting Range

Default

P1-01

Pump Mode

0, 3

0

Setting 0: Drive only

Designed for single pump stand-alone applications

Setting 3: MEMOBUS network

Up to eight drives can be networked together to provide for system redundancy and precise control.
Staging is disabled when and the drive PID output is influenced by the Water Level / Suction Pressure Control.
The functions listed below will behave slightly different when P1-01 is set to 3:
Start Level: Active on the first pump in the network. Drives in the process of alternation will not undergo this process.
Sleep: Active when the drive is the only drive running on the network.
Over-cycle Protection: Active when the drive is the only drive running on the network.
Pre-charge: Active only on the first drive to run in the network.
Low City Pressure: Active on any drive in the network. An alarm condition will cause other drives in the network to stop

running and show a “Net Pump Err” message.

Utility Delay: When this function is active, the drive is unavailable to the iQpump MEMOBUS Network and will force the

Home Screen text to show “Pump Off Network”.

Remote Drive Disable: When this function is active, the drive is unavailable to the iQpump MEMOBUS Network and will

force the Home Screen text to show “Pump Off Network”.

n

P1-02: System Units

Selects the base unit in which most drive PID setpoints, scaling, monitors, limits, and faults/alarm levels will be set.

Note:

Set this parameter prior to changing other parameters, as internal scaling is based on P1-02.

No.

Parameter Name

Setting Range

Default

P1-02

System Units

0 to 10

1

4.8 Detailed iQpump Parameter Descriptions

152

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual