Digital Operator Display

Error Name

Settings for N.C. and N.O. input for the following

functions were selected simultaneously:
• External Search Command 1 and External

Search Command 2 (61 vs. 62)

• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• KEB Command 1 and KEB Command 2 (65, 66

vs. 7A, 7B)

• FWD Run Command (or REV) and FWD/REV

Run Command (2-wire) (40, 41 vs. 42, 43)

• External DB Command and Drive Enable (60

vs. 6A)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

One of the following settings was entered while

H1-oo = 2 (External Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train

input selection is not set for the frequency

reference (H6-01 > 0)

• b1-15 or b1-16 set to 3 but no option card is

connected

• Although b1-15 = 1 (Analog Input) and H3-02

or H3-10 are set to 0 (Frequency Bias)

Correct the settings for the multi-function input terminal parameters.

H2-oo is set to 38 (Drive Enabled) and H1-oo

is not set to 6A (Drive Enable).

Digital Operator Display

Error Name

oPE04

Initialization Required, Term <–> Ctrl Chg

Cause

Possible Solutions

The drive, control board, or terminal board have

been replaced and the parameter settings between

the control board and the terminal board no longer

match.

• Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the drive.
• Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220.

Digital Operator Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(b1-01 = 3) and an input option card is not

connected to the drive.

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(b1-02 = 3) and an input option card is not

connected to the drive.
Frequency reference is assigned to the pulse train

input (b1-01 = 4) and terminal RP is not set for

frequency reference input (H6-01 > 0)

Set H6-01 to 0.

Digital Operator Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PID functions

conflict.

Cause

Possible Solutions

H3-02 and H3-10 are set to the same value.

Change the settings to H3-02 or H3-10 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 or H3-10

simultaneously.

The following simultaneous contradictory

settings:
• H3-02 or H3-06 = B (PID Feedback) while

H6-01

(Pulse Train Input) = 1 (PID Feedback)

• H3-02 or H3-06 = C (PID Target Value) while

H6-01 = 2

(pulse train input sets the PID target value)

Disable one of the PID selections.

5.4 Operator Programming Errors

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

193

5

Troubleshooting