Figure 4.58, Figure 4.59, For more information – Yaskawa iQpump Micro User Manual

Page 157: 8 detailed iqpump parameter descriptions, Figure 4.60 pre-charge normal acting pid

Advertising
background image

Run Command

Pre-Charge Level 2 (P4-32)

Pre-Charge Level (P4-01)

PID Feedback

Output Frequency

“Pre-Charge

Active” Message

& Digital Output

(H2-0X = A4)

P4-02 Pre-Charge Frequency

P4-06 Pre-Charge Frequency 2

P4-07

Pre-Charge Time 2

P4-03

Pre-Charge Time

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 0 (Normal Character)

Figure 4.58 Pre-Charge 1 and 2 Complete via PID Feedback

Run Command

“Pre-charge

Active”

Message &

Digital Output

(H2-0x = A4)

Output Frequency

P4-03

Pre-Charge Time

P4-02 – Pre-Charge Frequency

Pre-charge Level (P4-01)

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 0 (Normal Character)

PID Feedback

Pre-charge Level 2 (P4-32)

P4-07

Pre-Charge Time

P4-06 – Pre-charge Frequency 2

Figure 4.59 Pre-Charge 1 Complete via PID Feedback & Pre-Charge 2 via Timer

Pre-Charge

Complete via PID Feedback (Normal Acting PID)

PID
feedback

Output
frequency

“Pre-charge
Active”
Message &
Digital Output
(H2-0

☐ = A4)

Run
command

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 0 (Normal Character)

P4-01 Pre-charge Level

P4-02 Pre-charge Frequency

P4-03 Pre-charge Time

Figure 4.60 Pre-Charge Normal Acting PID

4.8 Detailed iQpump Parameter Descriptions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

157