H4: Analog Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-01

(041D)

Multi-Function Analog

Output Terminal AM

Monitor Selection

Term AM FuncSel

Selects the data to be output through multi-function analog

output terminal AM.

Set the desired monitor parameter to the digits available in

Uo-oo.

For example, enter “103” for U1-03.

Default: 102

Range: 000 to

999

151

H4-02

(041E)

Multi-Function Analog

Output Terminal AM

Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of the

selected monitor value.

Default: 100.0%

Min.: -999.9

Max.: 999.9

151

H4-03

(041F)

Multi-Function Analog

Output Terminal AM

Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

151

u

H5: MEMOBUS/Modbus Serial Communication

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H5-01

(0425)

<1>

Drive Node Address

Serial Comm Adr

Selects drive station node number (address) for MEMOBUS/

Modbus terminals R+, R-, S+, S-. Cycle power for the setting

to take effect.

Default: 1F

(Hex)

Min.: 0
Max.: FF

<2>

H5-02

(0426)

Communication Speed

Selection

Serial Baud Rate

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19.2 kbps

5: 38.4 kbps

6: 57.6 kbps

7: 76.8 kbps

8: 115.2 kbps

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Cycle power for the setting to take effect.

Default: 3

Range: 0 to 8

H5-03

(0427)

Communication Parity

Selection

Serial Com Sel

0: No parity

1: Even parity

2: Odd parity

0: No parity

1: Even parity

2: Odd parity

Cycle power for the setting to take effect.

Default: 0

Range: 0 to 2

H5-04

(0428)

Stopping Method after

Communication Error

(CE)

Serial Fault Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop

1: Coast to stop

2: Fast Stop

3: Alarm only

Default: 3

Range: 0 to 3

H5-05

(0429)

Communication Fault

Detection Selection

Serial Flt Dtct

0: Disabled

1: Enabled

0: Disabled

1: Enabled. If communication is lost for more than two seconds,

a CE fault will occur.

Default: 1

Range: 0, 1

H5-06

(042A)

Drive Transmit Wait

Time

Transmit WaitTIM

Set the wait time between receiving and sending data.

Default: 5 ms

Min.: 5

Max.: 65

H5-07

(042B) RTS Control Selection

RTS Control Sel

0: Disabled

1: Enabled

0: Disabled. RTS is always on.

1: Enabled. RTS turns on only when sending.

Default: 1

Range: 0, 1

H5-09

(0435)

CE Detection Time

CE Detect Time

Sets the time required to detect a communications error.

Adjustment may be needed when networking several drives.

Default: 2.0 s

Min.: 0.0

Max.: 10.0

H5-10

(0436)

Unit Selection for

MEMOBUS/Modbus

Register 0025H

CommReg 25h Unit

0: 0.1 V

1: 1 V

0: 0.1 V units

1: 1 V units

Default: 0

Range: 0, 1

H5-11

(043C)

Communications

ENTER Function

Selection

Enter CommandSel

0: Enter Required

1: No EnterRequired

0: Drive requires an Enter command before accepting any

changes to parameter settings.

1: Parameter changes are activated immediately without the

Enter command.

Default: 0

Range: 0, 1

B.7 H Parameters: Multi-Function Terminals

252