C.1 UL Standards

u

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada and indicates that UL has performed product testing

and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure C.1 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions

must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution severity 2 (UL standard).

n

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

u

IP66/NEMA Type 4X Conditions of Acceptability

Adhere to the installation conditions specified in this manual to take full advantage of the IP66/NEMA Type 4X design of this

drive.

n

Resistance Against Chemicals and Solvents

Table C.1

lists the information on chemical and solvent tolerability of the drive. The drive enclosure meets these requirements:

• UL50E: Enclosures for Electrical Equipment, Environmental Considerations NEMA Type 4X
• International Standard IEC 60529 Degrees of protection provided by enclosures (IP Code) IP66
Refer to the appropriate enclosure specification for more details on the enclosures resistance to chemicals and solvents.

Table C.1 Chemical and Solvent Tolerability

Reagent

Solvent

• Hydrochloric acid (10%)
• Sulfuric acid (10%)
• Nitric acid (10%)
• Ammonia water
• Sodium chloride

• Methanol
• Ethanol

NOTICE: Do not allow a stream of chemicals or solvents to be sprayed directly onto the drive enclosure. Failure to do so can damage the

drive.

NOTICE: Prevent moisture and other solvents from entering the drive enclosure when removing the front cover. Failing to do so can damage

the drive or considerably shorten its expected performance life.

u

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL Listed

closed-loop crimp terminals when wiring the drive main circuit terminals. Use only the tools recommended by the terminal

manufacturer for crimping. The wire gauges listed below are Yaskawa recommendations. Refer to local codes for proper wire

gauge selections.