H6: pulse train input – Yaskawa iQpump Micro User Manual

Page 253

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H5-12

(043D)

Run Command Method

Selection

Run CommandSel

0: FWD Run &REV

Run

1: Run & FWD/REV

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

Default: 0

Range: 0, 1

<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<2> When P1-01, Pump Mode, is set to 3 (MEMOBUS network), the range is dependent on P9-25, Highest Node Address.

u

H6: Pulse Train Input

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H6-01

(042C)

Pulse Train Input

Terminal RP Function

Selection

Term RP Func Sel

0: Frequency Ref

1: PID Feedback

2: PID Set Point

0: Frequency reference

1: PID feedback value

2: PID setpoint value

Default: 0

Range: 0 to 2

H6-02

(042D) Pulse Train Input

Scaling

Term RP Scaling

Sets the terminal RP input signal frequency that is equal to 100%

of the value selected in H6-01.

Default: 1440 Hz

Min.: 100

Max.: 32000

H6-03

(042E) Pulse Train Input Gain Term RP Gain

Sets the level of the value selected in H6-01 when a frequency

with the value set in H6-02 is input.

Default: 100.0%

Min.: 0.0

Max.: 1000.0

H6-04

(042F) Pulse Train Input Bias Term RP Bias

Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%

Min.: -100.0

Max.: 100.0

H6-05

(0430)

Pulse Train Input Filter

Time

Term RP Flt Time

Sets the pulse train input filter time constant.

Default: 0.50 s

Min.: 0.00

Max.: 2.00

H6-06

(0431)

Pulse Train Monitor

Terminal MP Selection Term MP Func Sel

Select the pulse train monitor output function (value of the

o-oo part of Uo-oo).

Refer to U: Monitors on page 278

for the list of U monitors.

Example: Select “501” for monitor U5-01. Select “0” when not
using this parameter or when using in the through mode.

<1>

Default: 102

Range: 0, 31,

101, 102, 116,

501, 502,

H6-07

(0432)

Pulse Train Monitor

Scaling

Term MP Scaling

Sets the terminal MP output signal frequency when the monitor

value is 100%.

Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor

output equal to the output frequency.

Default: 1440 Hz

Min.: 0

Max.: 32000

H6-08

(043F)

Pulse Train Input

Minimum Frequency

RP Lower Limit

Sets the minimum frequency for the pulse train input to be

detected. Enabled when H6-01 = 0, 1, or 2.

Default: 0.5 Hz

Min.: 0.1

Max.: 1000.0

<1> When set for sourcing, +5 V/1.5 k

Ω or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher. When set for sinking, the external power supply

should be +12 Vdc, ±5% with 16 mA or less.

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

253

B

Parameter List