Digital Operator Display

Fault Name

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02.

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).

Internal cooling fan is stopped

• Replace the cooling fan. .
• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.

Digital Operator Display

Fault Name

oH1

Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level.

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.

The internal cooling fan has reached its

performance life or has malfunctioned.

• Check the maintenance time for the cooling fan (U4-04).
• If U4-04 exceeds 90%, replace the cooling fan.
• After replacing fan, reset the fan maintenance time (o4-03 = “0”).

Current flowing to control circuit terminal

+V exceeded the tolerance level.

• Check the current level of the terminal.
• Set the current to the control circuit terminal to be 20 mA or less.

Digital Operator Display

Fault Name

oH4

Motor Overheat Fault (PTC Input)
• The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level.
• Detection requires setting multi-function analog inputs H3-02 or H3-10 to E.

Cause

Possible Solution

Motor has overheated

• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-04).
• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
• Check the motor rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.

Digital Operator Display

Fault Name

oL1

Motor Overload
The electronic motor overload protection tripped

Cause

Possible Solution

Load is too heavy

Reduce the load.

Cycle times are too short during

acceleration and deceleration

Increase the acceleration and deceleration times (C1-01 through C1-04).

5.2 Fault Detection

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

173

5

Troubleshooting