H3: multi-function analog inputs, For descriptions of setting values – Yaskawa iQpump Micro User Manual

Page 250

Advertising
background image

H2-oo

Setting

Function

LCD Display

Description

Page

4E

Braking transistor fault

(rr)

Brk Trans Fault

Closed: The built-in dynamic braking transistor failed.

–

4F

Braking resistor

overheat (oH)

BrkResistOvHeat

Closed: The dynamic braking resistor has overheated.

–

58

Underload detection

UL6

Closed: Underload is detected.

–

89

Output I Limit

Output I Lim

Closed: Drive output speed is being limited due to the output current limit or the

single phase foldback regulator.

–

8B

Lube Pump or Digital

Output Delay

Lube Pump or

DigitalOutput Delay

Closed: Refer to Lube Pump / Digital Output Delay parameters P4-30 and P4-31.

Display text is set by parameter P4-29.

–

8F

Internal Fan On

Internal Fan On

Internal Fan On

–

91

Pump Fault

Pump Fault

Closed when any of the following faults are active:
• Low feedback
• High feedback
• Low water
• High water
• NMS-Setpoint not met
• POC-Pump over cycle
• THMS-Thermostat input
• External pump fault

–

92

Transducer Loss

Transducer Loss

Closed: The analog output associated with PID feedback has risen above 21 mA

or fallen below 3 mA or a Transducer Loss alarm or fault is active.

–

93

Setptoint Not Met

SetPoint Not Met

Closed: During an “NMS-Setpoint Not Met” condition.

–

94

Loss of Prime

Loss of Prime

Closed: During an “LOP-Loss of Prime” condition.

–

95

Volute Thermostat Fault Volute-TStat Flt

Closed: Volute-Thermostat digital input is active.

–

96

High Feedback

High Feedback

Closed: During a “High Feedback” condition as defined by P1-11 and P1-14 OR

Closed: During a “High FB/Water” fault OR

Closed: During a “High Feedback” alarm

–

97

Low Feedback

Low Feedback

Closed: During a “Low Feedback” condition as defined by P1-08 and P1-14 OR

Closed: During a “Low FB/Water” fault OR

Closed: During a “Low Feedback” alarm

–

A2

Sleep Active

Sleep Active

Closed: The drive is not running due to the Sleep function (does not include Sleep

Boost).

–

A3

Start Delay

Start Delay

Closed: Feedback has risen above the start level (or fallen below for Inverse PID)

and the start timer is timing.

–

A4

Pre-Charge

Pre-Chg Active

Closed: Drive is in Pre-Charge mode.

–

A5

Anti-Jam Active

Anti-Jam Active

Closed: The anti-jam function is active (configured by P7-oo).

–

A9

Thrust Mode

Thrust Mode

Closed: The Thrust Bearing feature is active (output frequency is between 0 and

the value of P4-12).

–

AA

Utility Start Delay

Utility Delay

Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to

expire.

–

100 to

1AA

Function 0 to AA with

inverse output

–

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

–

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H3-01

(0410)

Terminal A1 Signal

Level Selection

Term A1 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

0: 0 to 10 V

1: -10 to 10 V

Default: 0

Range: 0, 1

149

H3-02

(0434)

Terminal A1 Function

Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: 0

Range: 0 to 41

149

H3-03

(0411)

Terminal A1 Gain

Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10 V is

input at terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

149

B.7 H Parameters: Multi-Function Terminals

250

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual