H3: multi-function analog inputs, For descriptions of setting values – Yaskawa iQpump Micro User Manual

Page 250

Advertising
background image

H2-oo

Setting

Function

LCD Display

Description

Page

4E

Braking transistor fault

(rr)

Brk Trans Fault

Closed: The built-in dynamic braking transistor failed.

4F

Braking resistor

overheat (oH)

BrkResistOvHeat

Closed: The dynamic braking resistor has overheated.

58

Underload detection

UL6

Closed: Underload is detected.

89

Output I Limit

Output I Lim

Closed: Drive output speed is being limited due to the output current limit or the

single phase foldback regulator.

8B

Lube Pump or Digital

Output Delay

Lube Pump or

DigitalOutput Delay

Closed: Refer to Lube Pump / Digital Output Delay parameters P4-30 and P4-31.

Display text is set by parameter P4-29.

8F

Internal Fan On

Internal Fan On

Internal Fan On

91

Pump Fault

Pump Fault

Closed when any of the following faults are active:
• Low feedback
• High feedback
• Low water
• High water
• NMS-Setpoint not met
• POC-Pump over cycle
• THMS-Thermostat input
• External pump fault

92

Transducer Loss

Transducer Loss

Closed: The analog output associated with PID feedback has risen above 21 mA

or fallen below 3 mA or a Transducer Loss alarm or fault is active.

93

Setptoint Not Met

SetPoint Not Met

Closed: During an “NMS-Setpoint Not Met” condition.

94

Loss of Prime

Loss of Prime

Closed: During an “LOP-Loss of Prime” condition.

95

Volute Thermostat Fault Volute-TStat Flt

Closed: Volute-Thermostat digital input is active.

96

High Feedback

High Feedback

Closed: During a “High Feedback” condition as defined by P1-11 and P1-14 OR

Closed: During a “High FB/Water” fault OR

Closed: During a “High Feedback” alarm

97

Low Feedback

Low Feedback

Closed: During a “Low Feedback” condition as defined by P1-08 and P1-14 OR

Closed: During a “Low FB/Water” fault OR

Closed: During a “Low Feedback” alarm

A2

Sleep Active

Sleep Active

Closed: The drive is not running due to the Sleep function (does not include Sleep

Boost).

A3

Start Delay

Start Delay

Closed: Feedback has risen above the start level (or fallen below for Inverse PID)

and the start timer is timing.

A4

Pre-Charge

Pre-Chg Active

Closed: Drive is in Pre-Charge mode.

A5

Anti-Jam Active

Anti-Jam Active

Closed: The anti-jam function is active (configured by P7-oo).

A9

Thrust Mode

Thrust Mode

Closed: The Thrust Bearing feature is active (output frequency is between 0 and

the value of P4-12).

AA

Utility Start Delay

Utility Delay

Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to

expire.

100 to

1AA

Function 0 to AA with

inverse output

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H3-01

(0410)

Terminal A1 Signal

Level Selection

Term A1 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

0: 0 to 10 V

1: -10 to 10 V

Default: 0

Range: 0, 1

149

H3-02

(0434)

Terminal A1 Function

Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: 0

Range: 0 to 41

149

H3-03

(0411)

Terminal A1 Gain

Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10 V is

input at terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

149

B.7 H Parameters: Multi-Function Terminals

250

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual