B.9 n: Advanced Performance Set-Up

The n parameters adjust more advanced performance characteristics.

u

n1: Hunting Prevention

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n1-01

(0580)

Hunting Prevention

Selection

Hunt Prev Select

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

n1-02

(0581)

Hunting Prevention

Gain Setting

Hunt Prev Gain

If the motor vibrates while lightly loaded, increase the gain by

0.1 until vibration ceases. If the motor stalls, decrease the gain

by 0.1 until the stalling ceases.

Default: 1.00

Min.: 0.00

Max.: 2.50

n1-03

(0582)

Hunting Prevention

Time Constant

Hunt Prev Time

Sets the time constant used for Hunting Prevention.

Default:

<1>

Min.: 0 ms

Max.: 500 ms

n1-05

(0530)

Hunting Prevention

Gain while in Reverse Hprev Gain @Rev

Sets the gain used for Hunting Prevention. If set to 0, the gain

set to n1-02 is used for operation in reverse.

Default: 0.00

Min.: 0.00

Max.: 2.50

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

n3: Overexcitation Braking

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n3-13

(0531)

Overexcitation

Deceleration Gain

Hflux Brake Gain

Applies a gain to the V/f pattern during deceleration (L3-04 =

4). Returns to normal values after ramp to stop or at re-

acceleration.

To increase the braking power of overexcitation, increase the

gain by 1.25 to 1.30.

Default: 1.10

Min.: 1.00

Max.: 1.40

n3-21

(0579)

High-Slip Suppression

Current Level

Hflux I Supp Lvl

Sets output current level at which the drive will start reducing

the overexcitation gain in order to prevent a too high motor slip

during Overexcitation Deceleration. Set as a percentage of the

drive rated current.

Default: 100%

Min.: 0

Max.: 150

n3-23

(057B)

Overexcitation

Operation Selection

Hflux Brake Sel

0: Enabled-Both Dir

1: Enabled-Fwd only

2: Enabled-Rev only

0: Enabled in both directions

1: Enabled only when rotating forward

2: Enabled only when in reverse

Default: 0

Range: 0 to 2