Run command

Baseblock

command

Output

frequency

During Run

Figure 4.43 During Run Time Chart

Setting 1: Zero Speed

Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.

Status

Description

Open

Output frequency is above the minimum output frequency set to E1-09 or b2-01

Closed

Output frequency is less than the minimum output frequency set to E1-09 or b2-01

OFF

Output frequency

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)

Figure 4.44 Zero-Speed Time Chart

Setting 2: Speed Agree 1 (f

ref

/f

out

Agree 1)

Closes when the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference regardless

of the direction.

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-02.

Note:

Detection works in forward and reverse.

L4-02

L4-02

Frequency
reference

Speed agree 1

ON

OFF

Output Frequency

or Motor Speed

Figure 4.45 Speed Agree 1 Time Chart

Setting 3: User-Set Speed Agree 1 (f

ref

/f

set

Agree 1)

Closes when the actual output frequency and the frequency reference are within the speed agree width (L4-02) of the

programmed speed agree level (L4-01).