Yaskawa iQpump Micro User Manual

Page 124

Advertising
background image

Figure 5.4

RS-485 Communication Connection

Modbus RTU Communications

RS-422/RS-485

19.2 Kbps

Terminating

Resistor

Figure 4.24 PC or PLC Connection Diagram

Setting 3: Option card

This setting requires entering the frequency reference via an option board plugged into connector CN5 on the drive control

board. Consult the option board manual for instructions on integrating the drive with the communication system.

Note:

If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming

Error will be displayed on the digital operator and the drive will not run.

To setup the drive to receive the “Auto Setpoint” for a network communication option card, set b1-01 to “3: Option PCB”,

and plug a supported communication option card into the drive control PCB. Consult the manual supplied with the option for

instructions on integrating the drive into the network system.

Setting 4: Pulse Train Input

This setting requires a pulse train signal to terminal RP to provide the frequency reference. Follow the directions below to

verify that the pulse signal is working properly.

Pulse Train Input Specifications

Response Frequency

0.5 to 32 kHz

Duty Cycle

30 to 70%

High Level Voltage

3.5 to 13.2 V

Low Level Voltage

0.0 to 0.8 V

Input Impedance

3 kΩ

Verifying the Pulse Train is Working Properly

• Set b1-01 to 4 and set H6-01 to 0.
• Set the H6-02 to the pulse train frequency value that equals 100% of the frequency reference.
• Enter a pulse train signal to terminal RP and check for the correct frequency reference on the display.

n

b1-02: Run Command Selection 1

Determines the Run command source 1 in AUTO Mode.
The drive comes factory programmed for Start and Stop from the keypad, but the user can program the drive to receive a Run

command from four different inputs: digital operator, terminals, serial communications, or an option PCB.

WARNING! Sudden Movement Hazard. Clear personnel, secure equipment, and check sequence and safety circuitry before starting the

drive. Failure to comply could result in death or serious injury from moving equipment.

To set the drive to receive the Run command from the HOA keypad, set b1-02 to “0: Operator,” and the HAND key will be

used to provide the Run command to the drive.
To set the drive to receive the Run command from the external terminals, set b1-02 to “1: Terminals” and initiate an external

Run command by a contact closure between terminals S1 and SN.

Note:

Using the external terminals requires setting the drive to AUTO Mode by pressing the AUTO key.

4.8 Detailed iQpump Parameter Descriptions

124

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising
This manual is related to the following products: