No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P5-05

(0D30) HAND Reference 2

HAND Reference 2

Sets the frequency reference used when HAND Mode 2 is

active.

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

P5-06

(0D31) HAND Ref. 1 Loss of

Prime Level

HandRef1 LOP Lvl

Detects loss of prime in the pump when in HAND Mode.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P5-02, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

P5-07

(0D32) HAND Ref. 2 Loss of

Prime Level

HandRef2 LOP Lvl

Detects loss of prime in the pump when in HAND Mode 2.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P5-05, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

P5-09

(0D34)

HAND References Set

via Motor Operated Pot

Selection

HAND MOP Sel

0: Disabled

1: Enabled

Selects whether parameters P5-02 and P5-05 are changed via

MOP from the home screen.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

<1> Unit text is set by P1-18, Prime Loss Detection Method.

u

P7: Anti-Jam

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P7-01

(0D90)

Anti-Jam Operation

Selection

Anti-Jam Sel

0: Disabled

1: Enabled

Enables and disables the anti-jam function.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

P7-02

(0D91) Anti-Jam Cycle Count AJ Cycle Count

Sets the maximum number of cycles that will be attempted

before triggering and Anti-Jam fault.

Default: 1

Min.: 1

Max.: 100

P7-03

(0D92) Anti-Jam Detection

Current Level

AJ Det I @Start

Sets the current level at start that will trigger the anti-jam

function.

Set as a percentage of the motor rated current.

Default: 120%

Min.: 50

Max.: 200

P7-04

(0D93) Anti-Jam Detection

Time at Start

AJ Det Tm@Start

Sets the length of time that current must rise above the level set

in P7-03 to trigger the anti-jam function.

Default: 0.3 s

Min.: 0.1

Max.: 2.0

P7-05

(0D94) Anti-Jam During Run

Current

AJ Det I @Run

Sets the current level during run that will trigger the anti-jam

function.

Set as a percentage of motor rated current.

Setting this parameter to 0 will disable anti-jam during run.

Default: 0%

Min.: 0

Max.: 200

P7-06

(0D95) Anti-Jam During Run

Time

AJ Det Tm @Run

Sets the length of time that the current must rise above the level

set in P7-05 to trigger the anti-jam function.

Restricted to simplex only.

Default: 0.3 s

Min.: 0.1

Max.: 2.0

P7-07

(0D96) Anti-Jam Frequency

Reference

AJ Freq Ref

Sets the maximum speed allowed when the anti-jam function is

active.

Default: 25.00

Hz

Min.: 0.00

Max.: 400.00

P7-08

(0D98) Anti-Jam Release Time AJ Release Time

Sets the length of time that the current must fall below the level

set in P7-03 to resume normal operation.

Default: 2.0 s

Min.: 0.5

Max.: 10.0

u

P9: Network Options

Parameters in this group are functional only when P1-01, Pump Mode, is set to 3 (MEMOBUS network).

B.11 P: Pump Parameters

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

271

B

Parameter List