8 detailed iqpump parameter descriptions – Yaskawa iQpump Micro User Manual

Page 158

Advertising
background image

PID
feedback

Output
frequency

“Pre-charge
Active”
Message &
Digital Output
(H2-0

☐ = A4)

Run
command

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 1 (Rev Character)

P4-01 Pre-charge Level

P4-02 Pre-charge Frequency

P4-03 Pre-charge Time

Pre-Charge

Complete via PID Feedback (Reverse Acting PID)

Figure 4.61 Pre-Charge Inverse Acting PID

Low Water
digital input
(N.O.)

Output
frequency

“Pre-charge
Active”
Message &
Digital Output
(H2-0

☐ = A4)

Run
command

P1-30 Low Water Digital Input = 0 (Normally Open)

Closed

P4-02 Pre-charge Frequency

P4-03 Pre-charge Time

Pre-Charge

Complete via “Low Water” Digital Input (N.O.)

Open

Figure 4.62 Pre-Charge via Low Water DI

PID
feedback

Output
frequency

“Pre-charge
Active”
Message &
Digital Output
(H2-0

☐ = A4)

Sleeping

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 1 (Rev Character)

P4-01 Pre-charge Level

P1-04 Start/Draw-Down Level

P4-03 Pre-charge Time

Pre-Charge & Sleep

Wake Below Pre-charge Level then Wake Above Pre-charge Level

Sleeping

P1-05
Start
Delay

b5-01 PID Select = 1 (Enabled) AND b5-09 Output Level Sel = 0 (Direct Acting)
NOTE A: Feedback is below the P4-01 level, Pre-charge is performed.
NOTE B: Feedback is above the P4-01 level, Pre-charge is NOT performed.

NOTE A

NOTE B

Figure 4.63 Pre-Charge and Sleep

4.8 Detailed iQpump Parameter Descriptions

158

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising
This manual is related to the following products: