3.7 I/O Connections

u

Sinking/Sourcing Mode Switch

Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing

mode; the drive is preset to sinking mode.

Table 3.13 Sinking/Sourcing Mode Setting

Set Value

Details

SINK

Sinking Mode (0 V common): default setting

SOURCE

Sourcing Mode (+24 V common)

DIP Switch S3

SINK

SOURCE

Figure 3.24 DIP Switch S3

n

Transistor Input Signal Using 0 V Common/Sink Mode

When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and use

the internal 24 V power supply.

Drive

Shielded cable

Forward run/stop

Not used

External fault N.O.

Fault reset

Multi-setpoint 1

HAND

HAND 2

Multi-function input

S1

S2

S3

S3

+24V

S4

S5

S6

S7

SC

SINK

SOURCE

SINK

SOURCE

Figure 3.25 Sinking Mode: Sequence from NPN Transistor (0 V Common)