B.2 b: Application

Application parameters configure the Run Command Source, Timer functions, PID control, and a variety of other application-

related settings.

u

b1: Operation Mode Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b1-01

(0180)

Frequency Reference

Selection 1

Ref Source 1

0: Operator

1: Analog Input

2: Serial Com

3: Option PCB

4: Pulse Input

0: Operator (will also switch PID setpoint to Q1-01)

1: Analog input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse input (terminal RP)

Default: 0

Range: 0 to 4

121

b1-02

(0181)

Run Command

Selection 1

Run Source 1

0: Operator

1: Digital Inputs

2: Communication

3: Option PCB

0: HOA keypad

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

Default: 0

Range: 0 to 3

124

b1-03

(0182)

Stopping Method

Selection

Stopping Method

0: Ramp to Stop

1: Coast to Stop

2: DCInj to Stop

3: Coast w/Timer

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

Default: 1

Range: 0 to 3

125

b1-04

(0183)

Reverse Operation

Selection

Reverse Oper

0: Reverse Enabled

1: Reverse Disabled

0: Reverse enabled

1: Reverse disabled

Default: 1

Range: 0, 1

b1-07

(0186)

Run Command

Retention when Source

is Changed

RunCmd@SrcChange

0: Require Cycle

1: Retain Run Cmd

Determines whether the run command is retained when the

Sequence Selection is changed

0: Require Cycle

1: Retain Run Command

Default: 0

Range: 0, 1

b1-08

(0187)

Run Command

Selection in

Programming Mode

RUN dur PRG Mode

0: Run

Disabled@PRG

1: ModeRun

Enabled@PRG

2: Prg only @ Stop

0: Run command is not accepted while in Programming Mode.

1: Run command is accepted while in Programming Mode.

2: Prohibit entering Programming Mode during run.

Default: 0

Range: 0 to 2

b1-11

(01DF)

Run Delay at Stop

(Back Spin Timer)

Run Delay @ Stop

Sets the amount of time that the drive will disallow the

reapplication of the Run command after the Run command is

lost. b1-11 is active for all b1-03 settings.

If set to zero and b1-03 = 3 (Coast to Stop w/ Timer), a

combination of C1-02 and output frequency determine the

length of time. Otherwise, no run delay will be applied.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

b1-12

(01E0)

Run Delay Memory

Selection

Run Dly Mem Sel

Determines whether the Run Delay Timer is saved to the

EEPROM during power loss.

0: Disabled

1: Only at Stop

2: Running & Stop

Note:

A JVOP-183 HOA Keypad must be plugged into

the drive for settings 1 and 2 to function. If the

keypad is removed, b1-12 will function as setting

0 (Disabled).

Default: 2

Range: 0 to 2

b1-14

(01C3) Phase Order Selection

Rotation Sel

0: Standard

1: SwitchPhaseOrder

0: Standard

1: Switch phase order (reverses the direction of the motor)

Default: 0

Range: 0, 1

b1-15

(01C4)

Frequency Reference

Selection 2

Ref Source 2

0: Operator

1: Analog Input

2: Serial Com

3: Option PCB

4: Pulse Input

Enabled when a multi-function digital input set for “External

Reference” (H1-oo = 2) closes.

0: Operator

1: Analog Input

2: Serial Communications

3: Option PCB

4: Pulse Input

Default: 0

Range: 0 to 4

B.2 b: Application

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

229

B

Parameter List