P4: pump advanced – Yaskawa iQpump Micro User Manual

Page 268

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P2-10

(0C6D) Sleep Mode: Cycling

Protection

Cycle Protection

Sets the maximum number of cycles that are allowed within the

time specified in P2-11 before tripping the PoC “Pump Over

Cycle” fault.

One cycle is defined when the drive transfers from normal

operation in AUTO Mode to Sleep Mode.

This function is active when the drive is running during AUTO

Mode. When P1-01 is set to 3 (MEMOBUS network), the

function is active when there is only one drive running on the

network.

Setting this parameter to 0 disables the function.

Default: 0

Min.: 0

Max.: 10

P2-11

(0C6E)

Sleep Mode: Maximum

Cycling Protection

Time

Max. Cycle Time

Sets the maximum time allowed between cycles. When no

cycling occurs within the programmed time, the drive will

decrease the internal cycle register.

Default: 300 s

Min.: 0

Max.: 3600

P2-12

(0C6F) Over Cycling Mode

Over Cycle Mode

0: Disabled

1: Alarm Only

2: Fault

3: Auto SP Comp.

0: Disabled

1: Alarm

2: Fault

3: Auto SP Compensation

Default: 0

Range: 0 to 3

P2-13

(0C70) Setpoint Compensation Setpoint Comp.

Allows for the software to automatically compensate the

setpoint in the event of excessive cycling.

Default: 0.0 PSI

<3>

Min.: 0.0

Max.: 6000.0

P2-14

(0C71)

Maximum Setpoint

Compensation

Max. SP Comp.

Sets the maximum allowed setpoint compensation for over-

cycling function.

Default: 0.0 PSI

<3>

Min.: 0.0

Max.: 6000.0

P2-23

(0C7A) Anti-No-Flow

Bandwidth

ANF Bandwidth

Sets the amount of PID error bandwidth used to detect the Anti-

No-Flow condition.

Avoid setting this parameter value too high, as operation may

become unstable.

Setting this parameter to 0.00 will disable the function.

Default: 0.40%

Min.: 0.00

Max.: 2.00

P2-24

(0C7B) Anti-No-Flow

Detection Time

ANF Det. Time

Sets the time delay before the drive starts the increased

deceleration rate after Anti-No-Flow is detected.

Default: 10.0 s

Min.: 1.0

Max.: 60.0

P2-25

(0C7C) Anti-No-Flow Release

Level

ANF Release Lvl

Sets the amount below the setpoint which the feedback must

drop to disengage the Anti-No-Flow and return to normal PID

operation.

Default: 3.0 PSI

<3>

Min.: 0.0

Max.: 100.0

<1> Display units vary depending on the setting for P2-01, Sleep Level Type. When P2-01 is set to 0, the display units are “Hz”; setting 1 is “A”; setting

2 is P1-02 Selection; setting 3 is “RPM”.

<2> Display units vary depending on the setting for P2-01, Sleep Level Type. When P2-01 is set to 0, 1, or 2, the display units are “Hz”; setting 3 is

“RPM”.

<3> Unit is determined by P1-02, System Units; scaling is determined by P1-03, Feedback Device Scaling; resolution is determined by b5-39, PID

System Units Display Digits.

u

P4: Pump Advanced

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P4-01

(0CFA) Pre-Charge Level

Pre-Charge Level

Runs the drive at the frequency set in P4-02.

The drive will exit Pre-charge when one of the following

conditions occurs:
• The feedback level rises above the level set in P4-01
• The pre-charge time set in P4-03 expires
• The low water digital input is deactivated (#8F) (if

programmed)

Default: 0.0 PSI

<1>

Min.: 0.0

Max.: 6000.0

155

P4-02

(0CFB) Pre-Charge Frequency Pre-Charge Freq.

Sets the frequency reference used when the Pre-Charge function

is active.

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

155

B.11 P: Pump Parameters

268

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual